Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual

Specifications

Specifications

Environmental

Temperature

Operating

Storage

0° to 40°C (32° to 104°F)
-15° to 30°C (5° to 86°F) charge the UPS battery every six

months
30° to 45°C (86° to 113°F) charge the UPS battery every three

months

This unit is intended for indoor

use only. Select a location sturdy

enough to handle the weight.
Do not operate the UPS where

there is excessive dust or the

temperature or humidity are

outside the specified limits.

Be sure the air vents on the

UPS are not blocked.

Environmental factors impact

battery life. High temperatures,

poor utility power, and frequent,

short duration discharges will

shorten battery life.

Maximum

Elevation

Operating

Storage

3,000 m (10,000 ft)
15,240 m (50,000 ft)

Humidity

0 to 95% relative humidity, non-condensing

Physical

Dimensions

H/W/D

133 mm x 483 mm x 673 mm
5.2 in x 19 in x 27 in

Weight

73 kg (161 lbs) shipping weight
63 kg (139 lbs) with battery module
37 kg (82 lbs) without battery module

63 kg (139 lbs)

Maximum Number of External Battery Packs Supported by the

Smart-UPS XL

10

Electrical

100 V models

120 V models

200 V models

230 V models

Output

Output Frequency

50/60 Hz +/– 3 Hz

Nominal Output Voltage

100 V

120 V

200 V

230 V

Input

Input Frequency

50/60 Hz +/– 3 Hz

Nominal Input Voltage

100 V

120 V

200 V

230 V