3.2 Mechanical Installation Details

The vibration switch must be fitted on the machine structure so that good transmission is

ensured from the likely source of excess vibration.

The vibration switch shall be firmly fixed in the vertical orientation shown in figure 1 to a vertical

surface of the vibrating machine using M5 fixings suitably resistant to vibration.

Figure 1: Mechanical installation to the surface of the vibrating machine

VERTICAL

124

51

Set Level Cap

Transport

Plug

M5 fixings

in the two

places

M5 fixings

in the two

places

Cable

Entry

Cap

Switch

Rating

Label

4. Electrical Installation

4.1 Introduction

• Do not exceed the switch contact ratings. The primary switching circuit is rated at 5 Amp

maximum and must be fused appropriately in line with the protected machine’s mains

supply and isolation device

• The DC-operated solenoid has a duty cycle of 25%. It is advised that a time limiter or

mono-stable device be fitted in line to automatically disconnect the solenoid supply after 30

seconds

• When connection is by a cord, the Earth wire connection must be longer than the Live and

Neutral wires, such that failure of the strain relief will cause the Earth wire to be the last

conductor interrupted

• To prevent water running down onto the vibration switch, add a ‘drip loop’ in any external

cabling

• For ambient temperatures below –10°C, use external wiring rated for the minimum ambient

temperature expected