Set-up sequence – Fire Fighting Enterprises Vibration Switch: Weatherproof User Manual

Page 6

Advertising
background image

6

Remove SET

LEVEL CAP.

With machine running,

reset switch.

Tripped ?

Tripped ?

Is an increase in

sensitivity required ?

Switch is set.

Retract SET LEVEL SCREW

steadily until tripped, then

advance 1/2 turn.

Y

Y

Y

N

N

N

Advance SET LEVEL SCREW

steadily 1/2 turn.

Reset switch.

Reset Machine.

5. Set-up Sequence

No adjustment is needed if the vibration switch has been ordered preset for your application.

The SET LEVEL can be checked by reference to the calibration curve in figure 6.

Adjust SET LEVEL so that the switch just no longer trips in normal running as follows: