System Overview ─ (continued)

The FireFinder XLS system has been seismic qualified

in accordance with:

ƒ

International Building Code, 2006 Edition

ƒ

California Building Code, 2007 Edition

ƒ

ASCE Standard 7, 2005 Edition

ƒ

OSHPD CAN 2-1708A.5, Rev. 3

ƒ

ICC-ES AC 156, Effective 1/1/2007

FireFinder XLS is also OSHPD preapproved under:
OSP-0057-10.

FireFinder XLS Components

The basic XLS control unit consists of the following sub-

assemblies: Person Machine Interface (Model PMI); Power

Supply (Model PSC-12); Device Loop Card (Model DLC);

Zone Indicating Card (Model ZIC-4A); Card cage (Model

CC-5); Inner Door Blank Single Plate (Model ID-SP); CAB-1,

CAB-2 or CAB-3 enclosures.
Optional modules that can be installed with the XLS System

include: Card Cage (Model CC-2); Network Interface Card

(Model NIC-C); Zone Indicating Card 8 circuits (Models ZIC-

8B / ZIC-2C); Control Relay Card (Model CRC-6); Output

Control Module (Model OCM-16); Switch Control

Module (Model SCM-8); LED Control Module (Model LCM-

8); Fan Control Module (Model FCM-6); Supervised Input

Module (Model SIM-16); Power Supply Extender (Model PSX-

12); Remote Network Interface (Model RNI); Remote

Printer Module (Model RPM); System Status Display

(Model SSD); Multi-Point Digital Alarm Communicator

(Model MDACT); Two-Module Remote Enclosure (Model

REMBOX2); Four-Module Remote Enclosure (Model

REMBOX4).
The XLS panel is compatible with a full line of intelligent

initiating devices, highlighted by the FirePrint application-

specified detectors: Models HFP-11 and HFPT-11. XLS is also

compatible with the NCC series of graphics command

centers.

PMI Person Machine Interface

PMI Person Machine Interface
The Person Machine Interface (Model PMI) is the core of the

FireFinder XLS system. Model PMI serves as both

operator interface and central microprocessor for the

FireFinder XLS system. From Model PMI, the end user can

acknowledge events, control the system-notification

appliance circuits and reset the system. Detailed

information about the nature and location of the events can

also be displayed.

Model PMI contains the site-specific program configuration

created in the Zeus system software-programming tool.

The controller in Model PMI provides all system logic and

supervision. Model PMI contains a large, 6" (1/4 VGA)

monochrome LCD display, touch screen and LEDs for

displaying system status. A sound is made when there is

any unacknowledged event from Model PMI. The display

is surrounded by keys that are used to control the

displayed information and to navigate through these

screens. Keys are also provided to obtain and enter "Help"

into the menu features of Model PMI.

The FireFinder system is controlled and operated from

Model PMI. The intuitive person machine interface uses

large, lighted buttons to prompt users as to the next

correct system operation that is available (Acknowledge,

Silence, Unsilence, Audible or Reset).

DLC Device Loop Card

DLC Device Loop Card
The DLC Device Loop Card (Model DLC) is the interface for

connection with FireFinder XLS detectors and initiating

devices

including manual stations, control and input

devices. Model DLC plugs into one (1) slot of the CC-2 or CC-

5 card cage. Programming Model DLC is accomplished

using the FireFinder XLS Zeus system software-

programming tool. Model DLC takes one (1) address on the

network, and communicates with two (2) device

circuits for a total of 252 detectors and devices. Model

DLC has 12 LEDs for diagnostic purposes, and provides

ground-fault detection and zone-isolation circuitry.