FIREPOWER Firefinder XLS User Manual

Page 5

Advertising
background image

s

Industry, Inc.

Building Technologies Division

All cards plugged into the CC-5 / CC-2 card cage

communicate with other FireFinder-XLS modules via a

common data bus. Connectors are provided on the left and

right side of the CC-5 to connect a 60-pin cable for

communications with the FireFinder-XLS' operator interface,

power supplies and amplifiers modules.
Field wiring to devices and circuits terminates on the

Models CC-5 / CC-2 card cages. All cards designed for use

with the Models CC-5 / CC-2 route their field wiring

terminations to the ‘top’ of the Model CC-5 / CC-2 card

cages. These connections are all power limited. Internal

wiring connections distribute 24VDC to cards or high-level

audio signals (depending on application used) connect to

the ‘bottom’ of the Model CC-5 / CC-2 card cages. These

connections are all non-power limited.
All wiring connections to the Model CC-5 / CC-2 card cages
are to removable terminal blocks. Terminal blocks are rated

for use with wire sized 12AWG to 24AWG. Each connector

is numbered to make wiring terminations to the correct

position on the terminal block simple in order to reduce

potential wiring errors.

SCM-8 Switch Control Module

SCM-8 Switch Control Module
The Switch Control Module (Model SCM-8) is a FireFinder

XLS-option module that provides manual control to the

Emergency Voice Evacuation System (EVAC) or manual

fire-system control. Each Model SCM-8 module provides

eight (8) momentary push-button switches and 16

light-emitting diodes (LEDs) to indicate their status.
Each switch is assigned two (2) LEDs, as well as a label

to indicate the switch's programmed usage. The label

slides behind a clear protective membrane. One of the

LEDs assigned to each switch is a dual-colored LED,

which is used to indicate what type of signal is active.
Each Model SCM-8 switch is fully programmable, and may
be used to control speaker circuits and a wide range of

general-system functions such as: All Call, All Evac,

Warden's Page, Speaker, etc. Any number of circuits may

be grouped and controlled by a single switch. Switch

usages and zone groupings are assigned using the Zeus

system software-programming software. Model SCM-8

modules are mounted on a hinged panel, as a part of the

FireFinder XLS Command Console enclosure.

LCM-8 LED Control Module

LCM-8 LED Control Module
The LED Control Module (Model LCM-8) is a FireFinder

XLS-option module that provides LED annunciation for
FireFinder XLS system activity. Each LCM-8 module

contains eight (8) groups of two (2) LEDs – each of which

can be assigned to desired outputs using the Zeus

system software-programming tool.
Eight (8) LEDs are dual-color capable (RED or GREEN,

flashing or steady). The remaining LEDs are AMBER

flashing or steady. A space is provided for labeling of LED

functions. The label slides behind a clear, protective

membrane. Model LCM-8 dimensions are identical to Model

SCM-8, and Model LCM-8 is mounted on the same hinged

panel, as a part of the FireFinder XLS Command Console

enclosure.

FCM-6 Fan, Motor, Dampers
Control

Module

FCM-6 Fan, Motor, Dampers Control Module
The Fan, Motor, Dampers Control Module (Model FCM-6) is a

FireFinder XLS command-console option module that

provides manual control of building HVAC system fans,

motors, and dampers. Each Model FCM-6 module provides

six (6) sets of three (3) push-button switches for manual-

system control. Each switch has three (3), associated

LEDs to indicate Fan / Damper / Motor status: OFF (Red LED),

ON (Green LED), TROUBLE (Yellow LED).

Advertising