ZIC-4A Zone Indicating Card

ZIC-4A Zone Indicating Card
The Zone Indicating Card (Model ZIC-4A) provides four (4)

fully supervised, programmable output circuits for use

on the FireFinder XLS Fire Alarm Control Panel. Model ZIC-

4A supplies four (4) Class B (Style Y) or Class A (Style Z) type

output circuits, power limited to 3.0 amps maximum per

circuit.
Each circuit can be independently programmed for use

with listed audible or visual notification appliances, listed

emergency audio speakers, municipal tie boxes, leased

lines, or as releasing circuits. Model ZIC-4A plugs into one

(1) slot in the Model CC-5 or Model CC-2 card cage, and has

on-board LEDs for system status and troubleshooting.

Indication of power, communication, internal operation,

and ground-fault conditions are provided, as well as

indication of circuit activation or trouble conditions.

ZIC-8B / ZIC-2C Zone Indicating Cards

ZIC-8B / ZIC-2C
The Zone Indicating Card (Model ZIC-8B) provides eight (8)

fully supervised, programmable output circuits for use on

the FireFinder XLS fire-alarm control panel (FACP). Model

ZIC-8B supplies eight (8) Class B (Style Y) type output

circuits, power limited to 2.0 amps maximum per circuit.

Each circuit can be independently programmed for use

with listed audible or visual notification appliances, or

listed emergency audio speakers. Model ZIC-8B plugs

into one (1) slot in the Model CC-5 or Model CC-2 card

cage, and has on-board LEDs for system status and

troubleshooting.
Model ZIC-2C mounts directly on Model ZIC-8B, and

allows each of the Model ZIC-8B output circuits to be used

for 2-channel voice applications. Indication of power,

communication, internal operation, and ground-fault

conditions are provided, as well as indication of circuit

activation or trouble conditions.

NIC-C Network Interface Card

NIC-C
The Network Interface Card (Model NIC-C) provides HNET or

XNET network communications between enclosures. In

addition to the HNET or XNET communication, Model NIC-C

provides CAN network communication within an enclosure

or external to the enclosure. HNET or XNET

communication can be wired Style 4 or Style 7, but the

CAN network can be wired Style 4 only.
When Model NIC-C is used for HNET communications, it

provides communication between enclosures on a single

system. When Model NIC-C is used for XNET

communications, Model NIC-C provides communication

between systems. The maximum of XNET Model NIC-C

cards on a single system (single node) is one (1), for a

total of 64 XNET Model NIC-C cards on a peer-to-peer

networked system.
Model NIC-C has diagnostic LEDs that indicate: Card Fail,

CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop ‘A’ Fail and

Loop ‘B’ Fail. Model NIC-C Card also has LEDs to indicate

Power, Style and Active Networks.

HLIM Line Isolator Module

HLIM Line Isolator Module
The loop-isolator module (Model HLIM) provides short-

circuit protection on FireFinder XLS intelligent device

circuits (see: Model DLC). When Model HLIM detects a

short circuit, Model HLIM is able to isolate the affected

segment of the circuit – allowing the remaining devices to
continue operation. Model HLIM is self-restoring

automatically reconnecting to circuit segment when the

fault is removed. Model HLIM can be wired in either a

Style 4 or Style 6 configuration.