Ransburg, Modes of operation – Ransburg Serial Node Adapter LECU4002_78553 User Manual

Page 11

Advertising
background image

MODES OF OPERATION

The Serial Node Adapter/Serial Node Adapter +

has three modes of operation, determined by what

modules need to be operated. The three modes

are: 1) MicroPak, 2) NPB (1 MicroPak, 1 Serial

Atomizer), and 3) Flex mode.

MicroPak Mode

MicroPak mode is for communication with the

MicroPak only, up to four units. This mode is

selected by setting SerNA dipswitch SW2-1 to

OFF. SW2, positions 5, 6, 7, and 8 must be set

to OFF. PLC data mapping information is shown

in Table 1 of the PLC I/O section.

NPB Mode

Node Per Bell mode communicates with one

MicroPak and one Serial Atomizer module and

is selected by setting SerNA dipswitch SW2-1 to

ON. SW2, positions 5, 6, 7, and 8 must be set to

OFF. PLC data mapping information is shown in

Table 2 of the PLC I/O section.

Flex Mode

Beginning with Serial Node Adapter/Serial Node

Adapter + version 2.02 software, this module has

the capability of communicating with one MicroPak

and any combination of Serial Atomizer (SerAT),

and Serial Digital (SerDG) modules, up to a total

of 12 modules.

Note: Serial Atomizer must

have version 3.0 or higher Eprom (77118-05)

and it's SW2-4 in ON position. Space is also

reserved for Serial Analog (SerAN) modules, pres-

ently under development. This is the FLEX mode

of operation. The new version 2.02 software is

completely compatible with the old MicroPak and

Node Per Bell modes as long as the Serial Node

Adapter/ Serial Node Adapter + dipswitch SW2

is set correctly. For these older modes, SW2,

position 5, 6, 7, and 8 must be set OFF, as is cur-

rently done on Serial Node Adapter modules with

software earlier than 2.02. With these settings,

the Serial Node Adapter/Serial Node Adapter +

looks the same to the PLC and other modules as

the older versions.

In the FLEX mode, on power up, before sending

data to modules, the Serial Node Adapter/Serial

Node Adapter + will read the local serial bus and

determine what module is in what location. It will

then read a group of three configuration words,

which are programmed into Block Transfer Writes

from the PLC. (The instructions for making up

these configuration words are given in Appendix

1). While making this comparison, the module will

flash its "CPU" indicator. If these two configura-

tions are the same, the Serial Node Adapter/Serial

Node Adapter + will begin communication with the

local modules, and the "CPU" indicator will stay

on solid. This method of redundant configuration

checking will prevent data from being sent to the

wrong module in case of a faulty module or one

having been removed. (PLC data mapping infor-

mation is shown in Table 3 of the PLC I/O Section.)

Flex Mode Settings

The setting of the four dipswitches, SW2, 5-8 is

critical to proper operation. (See Figure 6 entitled

"SW1, SW2, and SW3 Switches". ) In order to en-

able FLEX mode, SW2-1 must be ON. If SW2 - 1

is ON, the positions 5-8 mean:

Position 5:

OFF means the mode is determined by SW2-1,

either MicroPak only or NPB (one MicroPak and

one Serial Atomizer). In this mode the Serial

Node Adapter version 2.02 is backward compat-

ible with existing applications.

ON (with position 1 ON) means the new FLEX

mode. This means the PLC programmer must

include the configuration information in the first

three words of BTW.

Position 6 and 7:

These are used, as shown in Figure 1, to set the

logical rack size of the node adapter as it appears

to the PLC. The number of SerDG modules on

the bus determines the size.

Again, the Serial Node Adapter could do this

function automatically, but a faulty module or

modules removed could create an erroneous

reading.

Serial Node Adapter/Serial Node Adapter + - Introduction

Ransburg

7

LN-9238-02.3

Advertising