Maintenance – Robinair 34788-H Recovery, Recycling, Recharging Unit User Manual

Page 24

Advertising
background image

22

Maintenance

Scale Calibration Check

The calibration check is used to ensure that the
unit’s internal scale is always calibrated. During this
test, use only the calibration weight that is provided
with the unit.
1. Press Menu .
2. Use the arrow keys to scroll to CALIBRATION

CHECK.

3. Refer to Figure 18, and verify the magnet on the

bottom of the unit is clean. Press START / YES .

4. The display reads

ATTACH THE WEIGHT TO THE BOTTOM OF

THE MACHINE

PRESS START TO CONTINUE

5. Attach the weight provided to the magnet on the

bottom of the unit. Press START / YES .

• If the display shows CALIBRATION

APPROVED, the scale is in calibration. Press
any key to exit.

• If the display shows CALIBRATION REJECT,

the scale is out of calibration. Call your local
service center for assistance.

• If the display shows CALIBRATION ERROR

1, verify the calibration weight is correctly
attached to the magnet, and verify the magnet
is clean with nothing attached to it. If that does
not correct the problem, call your local service
center for assistance.

Check for Leaks

Check the unit for leaks every three months, or as
specified by law in your jurisdiction.
1. Turn off MAIN POWER, and disconnect the

power cord from the outlet.

2 . Open the rear door; remove top cover and front

panel .

3 . Use a leak detector to probe all connections

for refrigerant leaks. Tighten fittings if a leak is
indicated.

4. Reassemble the body panels, and close the

rear door.

Magnet

Figure 18

Inspect the unit periodically for leaks .
The manufacturer does not reimburse
for lost refrigerant .