Setup – Robinair 34788-H Recovery, Recycling, Recharging Unit User Manual

Page 9

Advertising
background image

7

560826 Rev. D, August 23, 2013

Setup

Fill the Internal Storage Vessel (ISV)

1 . Press START / YES, and the unit

automatically runs a 5-minute vacuum to
clear all internal air.

Note: The “burping” noise heard during this
process indicates air is being purged from the
system—this is normal.
2. After the vacuum pump shuts off, connect

the fill hose to the liquid connector on a
full source tank.

3. Open the source tank valve.
4. Install the source tank, and secure it to

the unit (using the tank strap) in such a
way that liquid refrigerant is supplied to
the connection.

5. Press START / YES to begin filling the

internal storage vessel. Add at least 8 lbs.
(3.6 kg) of refrigerant to ensure enough
refrigerant is available for charging.

This process takes 15–20 minutes. The

unit stops when a sufficient amount of
refrigerant has been transferred to the
internal tank, or when the source tank is
empty.

Press STOP / NO to pause. Press STOP

/ NO again to exit, or START / YES to
resume.

6. When the fill process is complete, press

STOP / NO to exit. The unit is ready for
operation.

Note: There is no need to calibrate the
scale; it is calibrated at the factory.

Figure 4

Side View

Fill Hose

(connect to

liquid line)

Power

Cord

Source

Tank

Strap

Low- and

High-Side

Hoses

Advertising