WARNING

The washer-extractor should be connected to an individual branch

circuit not shared with lighting or other equipment.

Electrical Specifications WF150, IWF150, IWF033, CWF033

150 liters / 33 pounds

Boiler Fed/Steam Heat

Electric Heat

Code

Voltage

Cycle

Phase

Wire

Full
Load Amps

Recommended Circuit

Breaker (US-market)

AWG/mm2

kW Standard

Heating Elements

Full
Load Amps

Recommended

Circuit Breaker (US-

market)

AWG/mm2

US NON-US

US NON-US

N

440-480 50/60

3

3+PE

4

10

10

14/2.5

6x3 kW

30

40

40

8/10.0

P

380-415 50/60

3

3+N+PE 12

15

16

14/2.5

38

50

50

8/10.0

Q

200-240 50/60

3

3+PE

12

15

16

14/2.5

57

70

70

4/25.0

X

200-240 50/60

1/3

2/3+PE

12

15

16

14/2.5

N/A N/A

N/A

N/A

Alternative Electric Heat Options

N

440-480 50/60

3

3+PE

3x3 kW +

3x2 kW

26

30

30

10/6.0

P

380-415 50/60

3

3+N+PE

34

40

40

8/10.0

Q

200-240 50/60

3

3+PE

50

60

60

6/16.0

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

3x3 kW +

3x4 kW

34

40

40

8/10.0

P

380-415 50/60

3

3+N+PE

53

60

60

6/16.0

Q

200-240 50/60

3

3+PE

N/A N/A

N/A

N/A

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

6x2 kW

21

30

30

10/6.0

P

380-415 50/60

3

3+N+PE

30

40

40

8/10.0

Q

200-240 50/60

3

3+PE

42

50

50

8/10.0

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

N

440-480 50/60

3

3+PE

6x4 kW

39

50

50

8/10.0

P

380-415 50/60

3

3+N+PE

47

60

60

6/16.0

Q

200-240 50/60

3

3+PE

N/A N/A

N/A

N/A

X

200-240 50/60

1/3

2/3+PE

N/A N/A

N/A

N/A

Table 3