moved, use (2) steel pipes thru the lift point, to lift gen-set. This mounting location of gen-set is important. It
must be installed in an area that is protected from harmful gases, liquids, dust, metallic particles, shock, or
vibrations. It should be installed in an outdoor location, so that exhaust fumes are vented to the atmosphere. The
factory installed weather and sound protected enclosure is designed to keep out undesirable weather elements.

WARNING

Unbalanced Weight
Improper lifting can
cause severe injury or
death and equipment
damage

Do not use lifting eyes.
Lift the generator set
using lifting bars
inserted through the
lifting holes on the skid.

Generator Lifting

Height

Width

Length

To lift the generator, always use spreader
bars,

chains,

eyehooks

and

other

hardware that is of sufficient strength to lift
at least three times the weight of the
generators

Lifting Bars

Lifting Bars

FIGURE 2

1. Exhaust

end must always be turned away or

parallel with building and minimum 5 feet away.

2. Exhaust end

is not to be directed towards

play areas, patios, under canopies or overhangs,
or where people or animals congregate.

3. Do not install generator under deck of house.

4. Furnace and other habited building air intakes

should be minimum 20 feet from exhaust end.

5. Windows and doors on adjacent walls, to be

closed at all times, during generator operation.

6. Nearest roof overhang vent or window locations

should be minimum 10 feet from exhaust end.

SUGGESTIONS FOR GENERATOR LOCATIONS

5'

5'

APPROX.

10'

OCCUPIED

BUILDING

PREFERRED

ACCEPTABLE

#

1

G

E

N

E

R

A

T

O

R

#

2

G

E

N

E

R

A

T

O

R

GAS

METER

DANGER

TOXIC FUMES

MAY ENTER

BUILDING

BUILDING AIR
INTAKE AREA

N

O

A

IR

IN

T

A

K

E

A

R

E

A

FIGURE 3