D. RESIDENTIAL GARAGE, CLOSET, AND ALCOVE INSTALLATIONS

Check with your local Authority Having Jurisdiction for requirements when installing boiler in a garage, closet, or alcove. Please read
the entire manual before attempting installation. Failure to properly take factors such as boiler venting, piping, condensate removal, and
wiring into account before installation could result in wasted time, money, and possible property damage and personal injury.

PRECAUTIONS
If the boiler is located in a residential garage, it should be installed per the latest edition of the National Fuel Gas Code, ANSI Z223.1,
and CGA-B149 Installation Code in Canada.

Mount the bottom of the boiler

a minimum of 18” above the floor of the garage, to ensure the burner and ignition devices are

well off the floor.

Locate or protect the boiler so it cannot be damaged by a moving vehicle.

For closet or alcove installations, a two pipe venting system must be used. Failure to follow this warning could result in substantial
property damage, severe personal injury, or death.

The space must be provided with correctly sized combustion/ventilation air openings for all other boilers located in the space with the
boiler. Do not install the boiler in an attic. Failure to comply with these warnings could result in substantial property damage, severe
personal injury, or death.

NOTE: For installations using room air for combustion, refer to the boiler venting section, Part 6 in this manual.

E. EXHAUST VENT AND INTAKE PIPE

Vent pipes must be properly supported. The boiler exhaust and intake connections are not designed to carry heavy weight. Vent
support brackets must be within 1’ of the boiler and the balance at 4’ intervals. Venting must be readily accessible for visual inspection
for the first 3’ from the boiler.

The boiler is rated ANSI Z21.13 Category IV (pressurized vent, likely to form condensate in the vent), and requires a special vent
system designed for pressurized venting.

You must also install air intake piping from outdoors to the boiler flue adaptor. NOTE: To prevent combustion air contamination, see
Table 2 in this section when considering exhaust vent and intake pipe termination.

Exhaust vent and intake pipe must terminate near each other and vented vertically through the roof. Venting methods are detailed in
the Venting Section. Do not attempt installation using any other means. Be sure to locate the boiler so exhaust vent and intake pipe can
be routed through the building and properly terminated. The exhaust vent and intake piping lengths, routing and termination method
must all comply with methods and limits given in the venting section.

F. PREVENT COMBUSTION AIR CONTAMINATION

Install intake piping for the boiler as described in the Venting section. Do not terminate exhaust in locations that can allow
contamination of intake air.

PRODUCTS TO AVOID

AREAS LIKELY TO HAVE CONTAMINANTS

Spray cans containing fluorocarbons

Dry cleaning/laundry areas and establishments

Permanent wave solutions

Swimming pools

Chlorinated waxes/cleaners

Metal fabrication plants

Chlorine-based swimming pool chemicals

Beauty shops

Calcium chloride used for thawing

Refrigeration repair shops

Sodium chloride used for water softening

Photo processing plants

Refrigerant leaks

Auto body shops

Paint or varnish removers

Plastic manufacturing plants

Hydrochloric or Muriatic acid

Furniture refinishing areas and establishments

Cements and glues

New building construction

Antistatic fabric softeners used in clothes dryers

Remodeling areas

Chlorine-type bleaches, laundry detergents, and cleaning solvents

Garages and workshops

Adhesives used to fasten building products