G. resetting the maintenance schedule – HTP EFT-399 User Manual

Page 68

Advertising
background image

68

LP-387 REV. 6.10.14

Function 24

Cascade Rotation

CASCADE ROTATION
48 HOURS 24

Sets the amount of hours before the first boiler in the cascade firing rotation will be changed. NOTE: If this parameter is
set to 0, the firing order of the boilers will not rotate. Default: 48 hours (Range: 0

– 240 hours).

Function 25

Cascade DHW Mode

NOT USED
NOT USED 25

Not used on this product.

Function 26

System Freeze Protect

SYS FREEZE PROT
PROTECT OFF 26

NOTE: This parameter is only present if the boiler is a cascade master. Allows the user to set the freeze protection
when a system pump is used. Factory Default: OFF. Selection of temperature activates freeze protection. (Range:
OFF, -40

o

F

– 104

o

F).

Function 27

Error System Sensor

ERROR SYSTEM SENS
ON 27

Allows the user to set the control to display an error message if the system sensor is open or shorted. NOTE: This
error does not stop the boiler (or boilers) from running. Factory Default: ON (Range: ON / OFF).

Function 28

Freeze Protection

FREEZE PROTECTION
ON 28

Allows the user to set freeze protection on the boiler. Factory Default: ON (Range: ON / OFF).

Function 29

DHW Modulation Mode

DHW MODULATE MODE
NORMAL MOD 29

This parameter controls how the boiler modulates for a DHW demand. In NORMAL MOD mode, the boiler will
modulate down from high fire when there is a DHW demand. In LOW MOD mode, the boiler will modulate up from low
fire when there is a DHW demand. This mode is useful to minimize short cycling when a large boiler and small indirect
tank are used together. Factory Default: NORMAL MOD (Range: NORMAL MOD / LOW MOD).

Function 30

Extra Boiler Mode

EXTRA BOILER MODE

OFF 30

Allows for a non HTP boiler to be controlled when the cascade output has risen above the percent of the cascade firing
rate set in this parameter. Factory Default: Off (Range: 50% - 100%).

Function 31

System Sensor Mode

SYSTEM SENSOR MODE
OFF 31

Suppresses the ‘NO FOLLOWER’ message on the display if the boiler is used as a cascade master boiler with no
follower boilers connected. Factory Default: OFF (Range: ON / OFF).

Function 32

Service Schedule

SERVICE SCHEDULE
OFF 32

Allows the user to select a service date or time based on the boiler run hours to program the boiler maintenance
schedule. Factory Default: OFF (Range: Date or Run Hours). NOTE: Without setting this function, Functions
33/34/35/36 will not display.

Table 20

– System Setting Menu Screens

NOTE: For the following functions, you must have your maintenance function turned on.


To change, press ENTER. The left most digit will begin to blink. Use the up

▲ or down ▼ arrows to change the digit. Use the  

arrow keys

to switch between digits. When you’ve made your selection, press ENTER again.

SCREEN

DESCRIPTION

Function 33

Year

SERVICE SCHEDULE
YEAR 00/00/2000 33

Allows the user to set the year of the next service reminder.

Hours

SERVICE SCHEDULE
10000’s

00

0000h 33

Allows the user to set the left two digits of the amount of run hours before next service reminder.

Function 34

Month

SERVICE SCHEDULE
MONTH 00/00/2000 34

If the date function was selected, this function allows the user to program the month. If you selected the run hour
function, you will need to program 10,000 hours, if required.

Hours

SERVICE SCHEDULE
10000’s 00

00

00 34

Allows the user to set the two middle digits of the amount of run hours for the next service reminder.

Function 35

Day

SERVICE SCHEDULE
DAY 00/00/2000 35

Allows the user to set the day of next service reminder.

Hours

SERVICE SCHEDULE
10000’s 0000

00

35

Allows the user to set the 2 right digits of the amount of run hours for the next service reminder.

Function 36

Telephone

TELEPHONE #
000 000 0000 36

Allows the user to input a telephone number that will be displayed when maintenance is required.

Table 21

– Maintenance Reminder Function Screens

G. RESETTING THE MAINTENANCE SCHEDULE

When the system control flashes MAINTENANCE REQUIRED, it is advisable that you call for service. After the service is performed,
reset the schedule for the next required service by using the following steps.

Advertising