4.4.20 Analog amplifier

Short description

This special function amplifies the value of an analog input

and outputs the result at an analog output.

Gain and offset parameters

Please note the information on gain and offset parameters in

Chapter 4.3.6.

Parameter p (number of decimals)

Applies only to the AQ value in a message text.

Functional description

The function fetches the analog signal of input Ax.
This value is multiplied by the value of the A (gain)

parameter, and parameter B (offset) is then added to the

product: (Ax•gain) + offset = actual value Ax.
The actual value Ax is output at AQ.

Symbol in IDEC

SmartRelay

Wiring

Description

Input Ax

You apply the analog signal to be
amplified at input Ax.
Use the analog inputs AI1...AI8

(

*

)

, the

analog memory markers AM1...AM6,
the block number of a function with
analog output, or the analog outputs
AQ1 and AQ2.

Parameter A: Gain

Range of values:

10.00

B: Zero offset

Range of values:

10,000

p: Number of decimals

Range of values: 0, 1, 2, 3

Output AQ This special function has an analog

output! This output can only be
connected with the analog input of a
function, an analog memory marker or
an analog output connector (AQ1,
AQ2).

Range of values for AQ:

-32767...+32767