IDEC SmartRelay installation and wiring

IDEC SmartRelay Manual

43

FL1B-J2B2

Note

Fluctuating analog values are due to screening on the connecting

wire from the analog valuator device to the analog FL1B-J2B2

expansion module (encoder wire) that has either been mounted

incorrectly or not at all.

To avoid fluctuating analog values when using these expansion

modules, proceed as follows:

•

Use only shielded encoder wires.

•

Shorten the encoder wire as much as possible. The encoder

wire must not be more than 10 meters long.

•

Clamp the encoder wire on one side only and clamp it only to

the PE terminal on the FL1B-J2B2 / FL1D-K2B2 / FL1D-K2BM2

expansion module.

•

Connect ground on the encoder supply to the PE terminal on the

expansion module.

Internal

Circuit

Analog Input (0-20mA)

Advertising