6 ELECTRICAL

CONNECTIONS

WARNING! READ SAFETY WARNING, ON PAGE 5, BEFORE USING THIS

CONTROL.

CAUTION! To avoid erratic operation, do not bundle AC line and motor connections
with potentiometer connections, voltage following connections, Start/Stop switch
connections, inhibit connections, or any other signal connections. Use shielded
cables on all signal connections over 12” (30 cm) long. Shield should be earth
grounded on the control

side only

.

Connect control in accordance with National Electric Code requirements and other local
codes that apply. The KBRG-212D does not contain AC line or armature fusing. It is
recommended that a 20 Amp fuse or circuit breaker be installed on each AC line
conductor not at ground potential. Connect control, in accordance with illustrations in this
section. A separate AC line switch or contactor must be connected as a disconnect switch
so that contacts open each ungrounded conductor. In addition, Table 6, details the
connection, wiring and torque information.


6.1 AC Line Connection – Connect the AC line to L1 and L2 terminals of TB1 as

shown in Figure 3, on page 14.

Note: There are no AC Line or Armature fuses supplied with this control. See Section

6.3, on page 14.

6.2 Motor Armature – Connect motor armature to terminal Ml and M2. (Be sure

jumper J3 is set to match motor voltage. See Figure 3, on page 14 and Section
7.2, on page 20.

TABLE 6 – TERMINAL BLOCK WIRING INFORMATION

Supply Wire Gauge

(AWG – Copper)

Terminal Block

Designation

Connection

Designation

Minimum

Maximum

Maximum

Tightening

Torque

(lbs- in)

TB1

Power / Control

Connections

22

14

3.5

TB2

L1, L2, M1, M2

18

12

3.5

TB3

F+, F-

22

14

3.5