CONFIGURING THE SM-PLUS DRIVE

Entering Program Mode:
To access the parameters, press the

Mode

button. This will activate

the password prompt. The display will read “00” and the right-hand
decimal point will be blinking as shown below. Use the and
buttons to scroll to the password value (the factory default password
is 225) and press

Mode

to enter.

1

2

5

6

11 12

2

14 13A 13B 13C

1

2

5

6

11 12

2

14 13A 13B 13C

Press

Mode

Display reads “00”

Upper right decimal point blinks

°

x

°

x

NO.

Parameter

Range of

Factory

Name

Adjustment

Default

01

Line Voltage

High (01), Low (02)

High (01)

02

Carrier Frequency

6 kHz (02)

03

Start Method

Normal (01)

04

Stop Method

Coast (01)

05

Speed Source

Keypad (01)

06

TB-14 Output

None (01)

13

TB-15 Output

None (01)

08

TB-30 Analog Out

None (01)

09

TB-31 Analog Out

None (01)

10

TB-13A Select

None (01)

11

TB-13B Select

None (01)

12

TB-13C Select

None (01)

14

Control

9600, 8, N, 2

15

Serial Link

with Timer (02)

SM-PLUS PARAMETER MENU

4 kHz (01), 6 kHz (02),

8 kHz (03), 10 kHz (04)

Normal (01), Start on Power-up (02),

Start w/DC Brake (03),

Auto Restart w/DC Brake (04),

Flying Restart 1 (05),
Flying Restart 2 (06),

Flying Restart 3 (07)

Coast (01), Coast with

DC Brake (02), Ramp (03),

Ramp with DC Brake (04)

Keypad (01), Preset #1 (02),

0-10 VDC (03), 4-20 mA (04)

None (01), Run (02), Fault (03),

Inverse Fault (04), Fault Lockout (05),

At Set Speed (06),

Above Preset #3 (07),

Current Limit (08), Auto Speed (09),

Reverse (10)

None (01), 0-10 VDC Freq (02),

2-10 VDC Freq (03),

0-10 VDC Load (04),

2-10 VDC Load (05)

None (01), 0-10 VDC Load (02),

2-10 VDC Load (03),

Dynamic Braking (04)

None (01), 0-10 VDC (02),

4-20 mA (03), Preset Speed #2 (04)

Decrease Freq (05), Jog Forward (06),

Jog Reverse (07), Auxiliary Stop (08)

None (01), 0-10 VDC (02),

4-20 mA (03), Preset Speed #1 (04),

Run Reverse (05), Start Reverse (06),

External Fault (07),

Remote Keypad (08), DB Fault (09),

Auxiliary Stop (10),
Accel/Decel #2 (11)

None (01), 0-10 VDC (02),

4-20 mA (03), Preset Speed #3 (04),

Increase Freq (05),
External Fault (06),

Remote Keypad (07),

DB Fault (08),

Accel/Decel #2 (09)

Terminal Strip Only (01),

Remote Keypad Only (02),

Terminal Strip or

Remote Keypad (03)

Disable (01)

9600, 8, N, 2 with Timer (02),

9600, 8, N, 2 , without Timer (03),

9600, 8, E, 1 with Timer (04),

9600, 8, E, 1, without Timer (05)

9600, 8, 0, 1 with Timer (06)

9600, 8, 0, 1 without Timer (07)

NO.

Parameter

Range of

Factory

Name

Adjustment

Default

16

Units Editing

Tenths of Units (01), Whole Units (02)

Whole Units (02)

17

Rotation

19

Acceleration Time

0.1 - 3600.0 sec

20.0 sec

20

Deceleration Time

0.1 - 3600.0 sec

20.0 sec

21

DC Brake Time

0.0 - 3600.0 sec

0.0 sec

22

DC Brake Voltage

0.0 - 30.0%

0.0%

23

0.0 - Maximum Frequency

0.0 Hz

24

Minimum Frequency - 240.0 Hz

60.0 Hz

25

Current Limit

30 - 180%

180%

26

Motor Overload

30 - 100%

100%

27

Base Frequency

25.0 - 500.0 Hz

60.0 Hz

28

Fixed Boost

0.0 - 30.0%

1.0%

29

Accel Boost

0.0 - 20.0%

0.0%

30

Slip Compensation

0.0 - 5.0%

0.0%

31-37

Preset Speeds

0.0 - Maximum Frequency

0.0 Hz

38

Skip Bandwidth

0.0 - 10.0 Hz

0.0 Hz

39

Speed Scaling

0.0 - 6500.0

0.0

40

Frequency Scaling

3.0 - 2000.0 Hz

60.0 Hz

41

Load Scaling

10 - 200%

200%

42

Accel/Decel #2

0.1 - 3600.0 sec

20.0 sec

43

Serial Address

1 - 247

1

44

Password

000-999

225

47

Clear History

Maintain (01), Clear (02)

Maintain (01)

User Settings (01),

48

Program Selection

OEM Settings (02), Reset OEM (03),

Reset 60 (04), Reset 50 (05)

50

Fault History

View Only

(N/A)

51

Software Code

View Only

(N/A)

52

DC Bus Voltage

View Only

(N/A)

53

Motor Voltage

View Only

(N/A)

54

Load

View Only

(N/A)

55

0-10 VDC Input

View Only

(N/A)

56

4-20 mA Input

View Only

(N/A)

57

TB Strip Status

View Only

(N/A)

58

Keypad Status

View Only

(N/A)

59

TB-30 Output

View Only

(N/A)

60

TB-31 Output

View Only

(N/A)

Maximum
Frequency

Minimum

Frequency

User Settings

(01)

Run/Stop

Contact

Speed Pot

Run/Stop

Contact

To add a potentiometer for speed control, change Parameter #5
(Standard Speed Source) to 0-10 VDC (03).

Once the PROGRAM mode is accessed, use the and

buttons

to scroll to the desired parameter number, and press the

Mode

button to see the parameter setting. Use the and

buttons to

change the parameter setting and press

Mode

to store the new

setting.

Connections:
Below is a sample wiring diagram for two-wire start/stop control.
The drive is ready to use right out of the box, with these simple con-
trol wiring connections; no parameter adjustments are required.
Speed is controlled from the and

buttons on the front of the

drive.

°

Use and to scroll to the password
value (factory default password is 225)

Press

Mode

to enter password

°

Forward Only (01),

Forward and Reverse (02)

Forward Only

(01)

Terminal Strip

(01)