Vanguard TRM-20_40 User Manual
Page 40

TRM-20 AND TRM-40 USER’S MANUAL
REV 1
36
d. The following screen will be displayed
Type the number of taps the LTC or Voltage Regulator has using the alpha-numeric
keypad, and then press the
[ENTER]
key. We will enter “3” for our example.
e. The following screen will be displayed:
If the tap information is correct, press the
[1]
key (YES) and continue to step f.
If the tap information is incorrect, press the
[2]
key (NO) and return to step d.
f. The following screen will be displayed:
Press the
[1]
key (V1, V2 RES TEST) if you would like to perform a V1 & V2 test. Continue
to step g.
Press the
[2]
key (V1 ONLY RES TEST) if you would like to perform a V1 test only.
Continue to step g.
1. V1, V2 RES TEST
2. V1 ONLY REST TEST
3 LOWER, -N-, 3 RAISE
IS THIS CORRECT?
1.YES
2.NO
ENTER NUMBER OF RAISE
TAPS, NOT COUNTING
NEUTRAL (1-23):