Vanguard TRM-20_40 User Manual

Page 43

Advertising
background image

REV 1 TRM-20 AND TRM-40 USER’S MANUAL

39

Press the

[ENTER]

key to confirm the reference temperature setting.

NOTE

The TRM will calculate the equivalent resistance value at this new
temperature.

k. The following screen will be displayed:

Press any key to continue.

l. The following screen will be displayed:

Set the LTC or Voltage Regulator tap position to the position indicated on the screen. To
change tap positions, press and hold the

[RAISE]

or

[LOWER]

LTC control button on

the front panel. Release the button when the tap position has been set to the position
indicated on the screen. Press the

[START]

key.

m. The following screen will be displayed momentarily:

calibrating

please wait...





- V1 & V2 TEST -

40 AMP TEST

set tap to 3 lower

"START" to RUN TEST

OR

"STOP" TO ABORT

***** WARNING! *****

DANGEROUS FLASH-OVER
WILL OCCUR IF CABLES
ARE DISCONNECTED!
********************