Alto-Shaam 10.20ESG User Manual

Page 15

Advertising
background image

G A S C O M B I T H E R M

I N S T A L L A T I O N M A N U A L

#MN-28676

PG

. 13

®

C O M B I T HE R M

V E N T I L AT I O N & I N S TA L L AT I O N R E Q U I R E M E N T S

1.

A single gas Combitherm oven requires a minimum of

28 CFM

make-up air for natural and propane gas.

Kitchen ventilation must include a provision for an
adequate flow of fresh air for gas combustion and to
prevent a negative-pressure condition. The bottom of
the oven provides air supply access for gas
combustion and must be kept clear at all times.
DO NOT

obstruct or restrict ventilation nor the air

flow required to support combustion.

2.

DO NOT

obstruct the flow of the exhaust flue at the

top rear of the oven. It is especially critical that gas
supply piping and electrical support cord and/or
receptacle be routed away from the path of the hot
combustion fumes.

3.

Make certain the oven installation maintains adequate
air ventilation to provide cooling for electrical and gas
components. The area around the oven should be
clear of any obstructions which might retard the flow
of cooling air. Failure to observe this caution may
result in damage to the components and will void the
warranty.

4.

This oven cannot be direct vented.

5.

Install the oven under a ventilation hood meeting all
applicable code requirements. Combustion fumes
must be vented in accordance with local, state, or
national codes.

Ventilating hoods and exhaust systems shall be

permitted to be used to vent appliances installed in

commercial applications.

Where automatically operated appliances are vented

through a ventilating hood or exhaust system equipped

with a damper or with a power means of exhaust,

provisions shall be made to allow the flow of gas to the

main burners only when the damper is open to a position

to properly vent the appliance and when the power means

of exhaust is in operation.

IN ACCORDANCE WITH

NFPA 54

COMMONWEALTH OF MASSACHUSETTS ONLY

.

An adequate ventilation system is required for commercial
cooking equipment. Information may be obtained by
writing to the National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269. When writing refer
to NFPA No. 96.

Inadequate ventilation, or failure to ensure
an adequate supply of fresh air will result in
a high ambient temperature at the rear of the
oven. An excessive ambient temperature
can cause the thermal-overload protection
device on the blower motor to trip resulting
in severe damage to the blower motor.

D A N G E R

Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certified service
technician qualified to work on
gas appliances.

D A N G E R

FAILURE TO VENT THIS APPLIANCE
PROPERLY MAY BE HAZARDOUS TO
THE HEALTH OF THE OPERATOR.
Equipment damage, operational
problems and unsatisfactory baking
performance may also be the
consequence of improper venting.
Any damage sustained by a failure to
properly vent this oven are not
covered under warranty.

C A U T I O N

DO NOT USE CIRCULATING FANS

ON THE FLOOR. FLOOR FANS WILL

AFFECT BURNER OPERATION.

C A U T I O N

To prevent malfunction or cause
negative back draft, DO NOT obstruct
exhaust flues or attach any flue
extension that will impede proper
burner operation.

Advertising
This manual is related to the following products: