FUNCTIONAL TESTING (GENERAL)

NOTE: Before performing any functional testing make

sure the Flame Guardian™ is disconnected to
prevent unwanted discharge. See Wiring
Diagram.

To perform any functional test, the following instruc-
tions should be followed.

1. Ensure that the Flame Guardian™ module(s) is/are

not connected to a power source.

2. Perform the desired Functional Test. Sound alarm

will go off.

3. Check fire zone.

4. Press the

SIGNAL SILENCE

button on the

Guardian™ Panel to suppress alarm.

5. Press the

SYSTEM RESET

button.

To proceed with testing:

• Restart procedure.

If testing has been completed:

• Reconnect the Flame Guardian™ module(s).

• Make sure the panel is in RUN mode.

NOTE: Notify all parties involved that you will be test-

ing the fire safety system; See Maintenance
Section.

FUNCTIONAL TEST (SPARK DETECTOR)

The easiest way to test the spark detectors is to
expose them to daylight. Both detectors must be test-
ed separately before the system is put into operation.

To perform the test, proceed as follows.

NOTE: Observe the functional testing instructions as

described in this section.

1. Loosen the mounting screw and remove one of the

spark detectors. That will expose the sensor to day-
light.

2. Check the system status. Guardian™ Panel should

indicate a fire in Zone 1.

3. Replace the spark detector and fasten it using the

mounting screw.

4. Press

SYSTEM RESET

button on the Guardian™

Panel.

5. Turn the Control Panel off for 10 seconds then back

on again.

6. Follow the same procedure for the other spark

detector.

NOTE: The spark detectors must be tested one by

one to make sure they both react to daylight.