FUNCTIONAL TESTING (GENERAL)
NOTE: Before performing any functional testing make
sure the Flame Guardian™ is disconnected to
prevent unwanted discharge. See Wiring
Diagram.
To perform any functional test, the following instruc-
tions should be followed.
1. Ensure that the Flame Guardian™ module(s) is/are
not connected to a power source.
2. Perform the desired Functional Test. Sound alarm
will go off.
3. Check fire zone.
4. Press the
SIGNAL SILENCE
button on the
Guardian™ Panel to suppress alarm.
5. Press the
SYSTEM RESET
button.
To proceed with testing:
• Restart procedure.
If testing has been completed:
• Reconnect the Flame Guardian™ module(s).
• Make sure the panel is in RUN mode.
NOTE: Notify all parties involved that you will be test-
ing the fire safety system; See Maintenance
Section.
FUNCTIONAL TEST (SPARK DETECTOR)
The easiest way to test the spark detectors is to
expose them to daylight. Both detectors must be test-
ed separately before the system is put into operation.
To perform the test, proceed as follows.
NOTE: Observe the functional testing instructions as
described in this section.
1. Loosen the mounting screw and remove one of the
spark detectors. That will expose the sensor to day-
light.
2. Check the system status. Guardian™ Panel should
indicate a fire in Zone 1.
3. Replace the spark detector and fasten it using the
mounting screw.
4. Press
SYSTEM RESET
button on the Guardian™
Panel.
5. Turn the Control Panel off for 10 seconds then back
on again.
6. Follow the same procedure for the other spark
detector.
NOTE: The spark detectors must be tested one by
one to make sure they both react to daylight.