MAINTENANCE
D-2
GUARDIAN CONTROL™ SOLUTIONS
TABLE D.1 – MAINTENANCE CALENDER
ITEM
ACTION
INTERVAL TIME IN
MINUTES
NOTES
FILTER UNIT MULTI DUST BANK
DUST BIN
Emptying the dustbin, depends on dust load, but is
expected to be once every 2 weeks.
Inspection hatches allow easy visual inspection.
Cleaning of the SparkShield unit is normally in line
with cleaning of the inside of the ducting. The unit
is installed by means of quick release clamps.
Also the unit itself has a divisible housing. Actual
time needed for cleaning is around 45-60 minutes.
Some cleaning detergent.
2 weeks
1 x per
year
10
15
CARD D
Replacement cartridges
1 x per
year
90
SPARK GUARDIAN™
DUST BIN
Emptying
4 weeks
10
Depends on dust load, but is
expected to be once every 4
weeks.
HOUSING
Inspection
Cleaning the inside: is normally in line with clean-
ing of the inside of the ducting.
2 x per
year
10
60
Inspection hatches in the duct-
ing.
Has no moving parts.
Inspection hatches allow easy
visual inspection. Cleaning
interval of the unit depends on
dust load, oil content and oper-
ating hours.
OIL GUARDIAN™
COMPLETE
UNIT
General inspection and cleaning.
1 x per
year
60
FILLING LIME
STONE
50Kg Lime stone adding to the lime feeder
1 x 2
weeks
30
DETECTION
SMOKE
DETECTORS
Check polluting percentage above sensor
4 weeks
15
SMOKE
DETECTORS
Dry run on normal
1 x per
year
60
TEMPERATURE
SENSORS
Dry run on normal
1 x per
year
60
SPARK
DETECTOR
Dry run on normal
1 x per
year
60
SUPPRESSION
FLAME
GUARDIAN™
Visual inspection
2 x per
year
60
FLAME
GUARDIAN™
Replacement
10 years
120