Installation, Warning caution – Lincoln Electric IM10063 TCV400 User Manual

Page 11

Advertising
background image

A-3

INSTALLATION

TCV400

A-3

Failure to follow these instructions can cause immedi-
ate failure of components within the machine. When
powering machine from a generator be sure to turn off
the machine first, before generator is shut down in
order to prevent damage to machine.

OUTPUT CABLE CONNECTIONS

The output leads are connected to the output termi-
nals marked “

+

” and “-

” (low inductance) or

- (high inductance). They are located at the
lower right and lower left corners of the front panel.
The TCV400 provides Tweco weld cable connector
receptacles.

OUTPUT CABLES

CABLE SIZES FOR COMBINED LENGTH OF ELEC-

TRODE AND WORK CABLE

400A

(100% DUTY

CYCLE)

500A

(50% DUTY

CYCLE)

MACHINE LOAD

CABLE LENGTHS

UP TO 50 ft

(15m)

50 to 100 ft

(15-30 m)

100-150 ft

(30-46 m)

150-200 ft

(46-61 m)

200-250 ft

(67-76 m)

3/0

85 mm

2

3/0

85 mm

2

3/0

85 mm

2

3/0

85 mm

2

4/0

107 mm

2

2/0

67 mm

2

2/0

67 mm

2

3/0

85 mm

2

3/0

85 mm

2

4/0

107 mm

2

FIELD INSTALLED OPTIONS

ELECTRIC SHOCK can kill.

Turn the power switch of the power

source “OFF” before installing plugs on
cables or when connecting or discon-
necting plugs to power source.

------------------------------------------------------------

WARNING

CAUTION

WHEEL KIT

For easy moving of the machine an optional platform
Wheel Kit 601547 is available.

Install per instructions provided with Wheel Kit.

METER KIT

Ammeter and Voltmeter Kit 610706 is available.