25

*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 Total input system transfer time = sample repetition

× 2 + internal operation time + 1 scan time.

As for revision “PV: 03 RL: 07 SV: 1.2”, the value is maximum time. Typ. 33ms + 1 scan time.
As for revision “PV: 04 RL: 08 SV: 2.0”, the value is maximum time. Typ. 26.5ms + 1 scan time.

*4 The 12-bit data (0 to 4095) and 10-bit data (0 to 1023) processed in the Analog I/O module can be linear

converted to a value between -32768 and 32767.
The Optional range designation and analog I/O data minimum and maximum values can be selected using
data registers allocated to analog I/O modules.

*5 As for voltage input data out of range (less than DC 0V, more than DC 10V), or current input data out of

range (less than DC 4mA, more than DC 20mA), the error code RGEF130 (Input data error) is output for
the analog module. Once the error occurs, input data from the point of the error is no longer updated. For
more information about error codes, read the “Maintenance/Troubleshooting Guide”.

*6 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it

is in the specified input range. Before inputting the value, therefore, consider the maximum error.

‹ Wiring

indicates a fuse.

• The power for the analog module

should be supplied separately from
the LT.
Turn the analog module on before
turning the LT on. Wait at least 30
seconds after power-off to restart the

external power-supply or it may not
operate properly.

• Be sure the analog OUT lines are

placed in a separate duct from high-
frequency, live lines such as high-volt-
age, high-power lines, inverters, etc.

Maximum Permanent Allowed Overload
(No Damage)

13 VDC

40 mA DC

Selection of Analog Input Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

Disconnection detection

No

External Connection

11-pin terminal connector

EXM-AMI2HT

Characteristics of Analog Voltage Inputs Voltage Input

Current Input

- +

+

-

+

-

+

-

IN0

IN1

+

-

NC

+

-

Analog voltage/
current output
device

Analog voltage/
current output
device

24 VDC

24
VDC

<EXM-AMI2HT>