*1 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value

between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.

Output Error Maximum Error at 25°C

(77°F)

±0.5% of full scale

Temperature Coefficient

±0.01% of full scale/°C

Repeatable after
Stabilization Time

±0.1% of full scale

Output voltage drop

±0.5% of full scale

Nonlinear

±0.2% of full scale

Output Ripple

1 LSB max.

Overshoot

0%

Total Error

±1% of full scale

Data

Digital Resolution

11 bits + sign

Output Value of LSB

±9.8 mV

Data Type in Application
Program

-2,048 to +2,047*

1

Custom range up to

-32768 to +32767

Current Loop Open

Not Detectable

Noise
Resistance

Maximum Temporary Deviation
during Electrical Noise Tests

±1% of full scale

Cable

Twisted-pair shielded cable is
recommended for improved noise immunity

Crosstalk

No crosstalk because of 1channel output

Voltage Endurance

2500 VAC by photocoupler between
outputs, external power supply and
internal logic circuits

Selection of Analog Output Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

External Connection

11-pin terminal connector

EXM-AVO2HT

Analog Output Specifications

Voltage Output