26

• Connect a fuse appropriate for the applied voltage and current draw, at the position shown

in the diagram.

• When the voltage input is open, the input into the unused channels is approx. 2.5 VDC for

revision

PV: 03 RL: 07 SV: 1.2” and 0 VDC for revision “PV: 04 RL: 08 SV: 2.0”.When

the voltage input is short circuited, 0 VDC is input to them. Please shortcircuite to
prevent from the invalid values input. When the current input is open, error code
(RGEF130 input data error) occurs to the unused channels, then the invalid values are
input. The voltage input settings is recommended to the unused channels.

• The (-) poles of inputs IN0 and IN1 are connected internally.

15.7 4-ch Analog input / Temperature input module

The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated input
voltage ranges from DC19.2 to 30 V including ripple. The consumption current is 60 mA
(24 VDC) when the input is not-open, output 100%. You can input voltage, current, or
temperature probes on up to 4 channels. You cannot use different types of input at the same
time.

EXM-AMI4LT

Characteristics of Analog Voltage Inputs

Voltage Input

Current Input

Temperature Probes

Input Range

DC0 to 10 V

DC0 to 20 mA

(RTD)
Pt100/Pt1000/
Ni100/Ni1000,
3-wire type
Pt sensor: -200
to +600°C (-328
to +1112°F)
Ni sensor: -50 to
+150°C (-58 to
+302°F)

Input Impedance

10 k

 min.

250

 max.

10 k

 min.

Input Points

4 points

A-D Conversion Sample

Repetition Time

160 ms

Total Input
System
Transfer Time*

1

4x160 ms + 1 scan time

8x160 ms + 1
scan time

Input Type

Non differential input

Operating Mode Self-scan
Conversion Mode

 type ADC

Input Error

Maximum Error
at 25°C (77°F)

±0.2% of full scale
±0.4% temperature probe input

Temperature
Coefficient

±0.005% of full scale/°C

Advertising