11 2-ch analog-input/1-ch analog-output module, 11 2-ch analog-input/1-ch analog, Output module – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 35: Wiring
35
Wiring
indicates a fuse.
• The power for the analog module should be supplied separately from the LT. Turn
the analog module on before turning the LT on. Wait at least 30 seconds after
power-off to restart the external power-supply or it may not operate properly.
• Use the braid supplied with the module to connect the functional ground.
• Connect an appropriate fuse for the applied voltage and current draw, at the position
shown in the diagram.
• To avoid disturbances on the analog outputs, the power supply of the EXM-AVO2HT
module must be turned on or off at the same time than the base controller power supply.
15.11 2-ch analog-input/1-ch analog-output module
The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated
input voltage ranges from DC20.4 to 28.8 V The consumption current is 45 mA
*1
or
50 mA
*2
(24VDC) when the input is not-open, output 100%. You can select either voltage or
current for each inpu or output channel.
EXM-AMM3HT
Characteristics of Analog Voltage Inputs
Voltage Input
Current Input
Input Range
From DC0 to 10V
From DC4 to 20 mA
Input Impedance
1 M
min.
10
Input Points
2 points
A-D
Conversion
Sample Repetition Time
20 ms max.
Total Input System Transfer
Time*
3
105 ms + 1 scan time*
1
60 ms + 1 scan time*
2
Input Type
Single-ended input
Differential input
Operating Mode
Self-scan
Conversion Mode
type ADC
(1)
(1)
+
-
0 V
+
0 V
0 V
0 V
0 V
+
0 V
0 V
(1) Voltage/current preactuator
OUT1
OUT 2
<EXM-AVO2HT>