11 2-ch analog-input/1-ch analog-output module, 11 2-ch analog-input/1-ch analog, Output module – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 35: Wiring

Advertising
background image

35

 Wiring

indicates a fuse.

• The power for the analog module should be supplied separately from the LT. Turn

the analog module on before turning the LT on. Wait at least 30 seconds after
power-off to restart the external power-supply or it may not operate properly.

• Use the braid supplied with the module to connect the functional ground.

• Connect an appropriate fuse for the applied voltage and current draw, at the position

shown in the diagram.

• To avoid disturbances on the analog outputs, the power supply of the EXM-AVO2HT

module must be turned on or off at the same time than the base controller power supply.

15.11 2-ch analog-input/1-ch analog-output module

The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated
input voltage ranges from DC20.4 to 28.8 V The consumption current is 45 mA

*1

or

50 mA

*2

(24VDC) when the input is not-open, output 100%. You can select either voltage or

current for each inpu or output channel.

EXM-AMM3HT

Characteristics of Analog Voltage Inputs

Voltage Input

Current Input

Input Range

From DC0 to 10V

From DC4 to 20 mA

Input Impedance

1 M

 min.

10

Input Points

2 points

A-D
Conversion

Sample Repetition Time

20 ms max.

Total Input System Transfer
Time*

3

105 ms + 1 scan time*

1

60 ms + 1 scan time*

2

Input Type

Single-ended input

Differential input

Operating Mode

Self-scan

Conversion Mode

 type ADC

(1)

(1)

+

-

0 V

+

0 V

0 V

0 V

0 V

+

0 V

0 V

(1) Voltage/current preactuator

OUT1

OUT 2

<EXM-AVO2HT>

Advertising