15.13 Thermocouple Pt100 input/1-ch analog-output module

The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated
input voltage ranges from DC20.4 to 28.8 V. The consumption current is 40 mA

*1

or

50 mA

*2

(24 VDC) when the input is not-open, output 100%.

EXM-ALM3LT

Characteristics of Thermocouple
& Temperature Inputs

Thermocouple

Temperature Probes

Input Range

Type K:
0 to 1300°C/32 to 2372°F
Type J:
0 to 1200°C/32 to 2192°F
Type T:
0 to 400°C/32 to 742°F

(RTD)
Pt 100, 3-wire type
(-100 to 500°C)
(-148 to 932°F)

Input Impedance

1 M

Ω min.

A-D
Conversion

Sample
Repetition Time

20 ms max.

20 ms max.*

1

40 ms max.*

2

Total Input System
Transfer Time*

3

200 ms + 1 scan time*

1

60 ms + 1 scan time*

2

200 ms + 1 scan time*

1

80 ms + 1 scan time*

2

Input Type

Differential input

Operating Mode

Self-scan

Conversion Mode

Σ∆ type ADC

Input Error

Maximum Error
at 25°C (77°F)

±0.2% of full scale plus
reference Junction
compensation accuracy
±4°C max

±0.2% of full scale

Temperature
Coefficient

±0.006% of full scale/°C

Repeatable after
Stabilization Time

±0.5% of full scale

Nonlinear

±0.2% of full scale

Maximum Error

±1% of full scale

Data

Digital
Resolution

All types:
4,096 increments (12 bits)*

1

Type K:
13,000 increments (14 bits)*

2

Type J:
12,000 increments (14 bits)*

2

Type T:
4,000 increments (12 bits)*

2

4,096 increments (12 bits)*

1

6,000 increments (13 bits)*

2

Input Value of
LSB*

4

Type K:
0.325°C/0.585°F*

1

Type J:
0.300°C/0.540°F*

1

Type T:
0.100°C/0.180°F*

1

All types:
0.100°C*

2

/0.180°F*

2

0.15°C/0.27°F*

1

0.100°C/0.180°F*

2

Advertising