Digital events, General software – Watlow Series 988 User Manual

Page 122

Advertising
background image

8.8

WATLOW Series 988 User’s Manual

General Software Features, Chapter 8

General Software

Digital Events

Requirements
A single digital event input is standard on all controls. A second digital
input is available as an option for input 2 (98_ _-_5_ _-_ _ _ _).

Overview
The digital event input options on the Series 988 controller allow the oper-
ator to select one of several software functions with the close of a cus-
tomer-supplied switch or by a change in dc voltage (See

Chapter 2

for volt-

age and wiring information.).

The list below outlines the functions that can be controlled with a digital
event input:

• Idle set point [IdSP] lets the operator select a second (idle) set point.

• Turn control outputs off [`OFF] inhibits the control outputs.

• Alarm reset [`ALr] resets alarms from a remote location.

• Switch PID sets [`Pid] selects between PID set A or B (requires
enhanced software, 98_B-_ _ _ _-_ _ _ _).

• Remote set point [`rsp] switches to remote set points.

• Front panel lockout [`LOC] locks out the front panel keys to prevent
tampering.

• Control output action [Actn] switches the control action of outputs 1
and 2 from heating to cooling, or vice versa.

• Auto/Manual operation [A-M] switches to the manual mode of opera-
tion at the percent power selected with [FAIL] (Global Menu) and disables
the Auto/Man key.