Rtd1] [ftr1, Setup-input, Rtd (100 ω ) calibration curve 1 – Watlow Series 988 User Manual

Page 34: Software filter 1

Advertising
background image

WATLOW Series 988 User’s Manual

4.7

Setup Menus, Chapter 4

Setup-Input

RTD (100

Ω

) Calibration Curve 1

Select the calibration curve for the RTD 1 input. The RTD input uses
either the European (DIN, 0.003850

Ω

/

Ω

/°C) or the Japanese (JIS,

0.003916

Ω

/

Ω

/°C) linearization standard.

[rtd1] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].

Default

↓

[`din]

…

[`JIS]

[rtd1]

[rtd1]

Software Filter 1

Select the filter time constant, in seconds, for input 1. This smooths a
rapidly changing input signal for display or control purposes.

• Select a positive value to filter only the display.

• Select a negative value to filter the input signal.

• Set the value to [```0] to disable the filter.

[Ftr1] This prompt always appears.

Default

↓

[`-60]

…

[```0]

…

[``60]

[Ftr1]

[Ftr1]

[Ftr1]

[rtd1]

[Ftr1]