Lat2] [sil2, Setup-output, Latching 2 – Watlow Series 988 User Manual

Page 51: Silencing 2

Advertising
background image

4.24

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

Setup-Output

Latching 2

Select whether alarm 2 will be latching or non-latching. A latching
alarm [`LAt] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.

[LAt2] This prompt appears only on controllers equipped with output 2
hardware and with [`Ot2] set to [`AL2] or [AL2n].

Default

[`nLA]

[`LAt]

[LAt2]

[LAt2]

Silencing 2

Select silencing to inhibit alarm 2 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between [A2LO] and

[A2HI].

[`AL2] This prompt appears only on controllers equipped with output 2
hardware and with [`Ot2] set to [`AL2] or [AL2n].

Default

[`OFF]

[``On]

[SIL2]

[SIL2]

˜

NOTE:
See

Chapter 7

for

more information
on alarms.

[LAt2]

[SIL2]

Advertising