Lat2] [sil2, Setup-output, Latching 2 – Watlow Series 988 User Manual
Page 51: Silencing 2
4.24
WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Latching 2
Select whether alarm 2 will be latching or non-latching. A latching
alarm [`LAt] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.
[LAt2] This prompt appears only on controllers equipped with output 2
hardware and with [`Ot2] set to [`AL2] or [AL2n].
Default
↓
[`nLA]
[`LAt]
[LAt2]
[LAt2]
Silencing 2
Select silencing to inhibit alarm 2 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A2LO] and
[A2HI].
[`AL2] This prompt appears only on controllers equipped with output 2
hardware and with [`Ot2] set to [`AL2] or [AL2n].
Default
↓
[`OFF]
[``On]
[SIL2]
[SIL2]
˜
NOTE:
See
for
more information
on alarms.
[LAt2]
[SIL2]