Setup-Output

Output 2

Set the way that output 2 will respond to a difference between the set
point and an input variable.

• [`AL2] de-energizes output 2 in an alarm condition.

• [AL2n] energizes output 2 in an alarm condition.

• [``Ht] select reverse action, so that output 2 responds when the input

signal is less than the set point.

• [``CL] select direct action, so that output 2 responds when the input

signal is more than the set point.

[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98_ _-_ _ _A-_ _ _ _). [`AL2] and [AL2n] do not appear if out-
put 2 is a process output (98_ _-_ _ _F-_ _ _ _). [``Ht] and [``CL] do not
appear if [AL90] (in the Global Menu) is set to [dUPL].

Default

[``no]

[`AL2]

[Al2n]

[``Ht]

[``CL]

[`Ot2]

[`Ot2]

[`Ot2]

[`Ot2]

[`Ot2]

Process 2

Select the process range for output 2.

[Prc2] This prompt appears only on controllers equipped with output 2
process hardware (98_ _-_ _ _F-_ _ _ _) and with [`Ot2] not set to [``no].

Default

4-20mA

0-20mA

0-5V

Î

1-5V

Î

0-10V

Î

(dc)

[4-20]

[0-20]

[`0-5]

[`1-5]

[0-10]

[Prc2]

[Prc2]

[Prc2]

[Prc2]

[Prc2]

[`Ot2]

[Prc2]