Input 1 wiring, Thermocouple or 0-50mv (high impedance) – Watlow Series 988LF User Manual

Page 17

Advertising
background image

WATLOW Series 988LF User’s Manual

2.7

Installation and Wiring, Chapter 2

Figure

2.7

c —

0-5V

О

О

, 1-5V

О

О

or 0-10V

О

О

(dc) Process

Universal signal conditioner

98 _ L - 2 _ _ _ - A A _ _

Input impedance: 10K

Figure

2.7

a —

Thermocouple or 0-50mV (high impedance)

Thermocouple only

98 _ L - 1 _ _ _ - A A _ _ (no DIP switches)

Universal signal conditioner

98 _ L - 2 _ _ _ - A A _ _

Input impedance: 20M

Figure

2.7

b —

RTD (2 or 3 Wire) 100

Universal signal conditioner

98 _ L - 2 _ _ _ - A A _ _

9

10

+

-

0-50mV

9

10

8

S2

S1

S3

10

9

-

+

Figure

2.7

d —

0-20mA or 4-20mA Process

Universal signal conditioner

98 _ L - 2 _ _ _ - A A _ _

Input impedance: 7

10

8

-

+

9

10

8

S2

S1

DIP Switch

Setting

R, S, B

DIP Settings

J, K, T, N, C, E, D, Pt2,

0-50mV DIP Settings

DIP Switch

Setting

DIP Switch

Setting

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

O
N

1

2

3

O
N

1

2

3

O
N

1

2

3

9

10

+

-

Jumper

#9 to #10

for 2 wire

RTD

Input 1 Wiring

O
N

1

2

3

O
N

1

2

3

ç

CAUTION:
An external resistor
is required for
0-20mA and 4-20mA
process wiring to
prevent a high in-
rush current which
could burn out the
controller’s 7-ohm
resistor. See page
2.4 for recommen-
dations.

Advertising