Rtd calibration curve, Setup, Rl1] [`rh1 – Watlow Series 988LF User Manual
Page 27

Setup
Setup Menu, Chapter 4
WATLOW Series 988LF Users Manual
4.5
[`rL1]
[`rH1]
Range Low and Range
High continued from
previous page.
NOTE:
The range high
[`rH1]
value for process
inputs can be extended
to
[9999]
.
Default
Default
Default
Default
↓
↓
↓
↓
``°F]
[`°C]
[`rL1] [`rH1]
[`rL1] [`rH1]
[```b]
[``32]…[3300]
[```0]…[1816]
[`rtd]
[-328]…[1472]
[-200]…[`800]
[`r†d]
[-9(9]…[99(9]
[-7#3]…[53&7]
process
[4-20]
[-999]…[`999]
units
[0-20]
[-999]…[`999]
units
[`0-5]
[-999]…[`999]
units
[`1-5]
[-999]…[`999]
units
[0-10]
[-999]…[`999]
units
[0-50]
[-999]…[`999]
units
RTD Calibration Curve
Select the RTD calibration curve. The RTD input uses either the
European (DIN, 0.003850 ohms/ohms/°C) or Japanese (JIS, 0.003916
ohms/ohms/°C) linearization standard.
[`rtd] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].
Default
↓
[`din]
[`J15]
[`rtd
[`rtd
[`rtd]