<3. Operation>

3-10

IM 01C25T03-01E

a. Display Selection (I10: DISP OUT1)

Select the variable for the parameter I10: DISP

OUT1 to display on the integral indicator.

• Example: Change the integral indicator scale

from % of range to input pressure

display.

ESC

SET

I10:DISP OUT1

PRES

FEED

NO

OK

Use the or key
to select

PRES.

Press the key twice to
enter the setting.

Press the (OK) key.

F0321.ai

SET

I10:DISP OUT1

PRES %

< PRES >

< PRES % >

< ENGR.PRES >

< SP >

b. Cyclic Display (I11: DISP OUT2, I12: DISP

OUT3, and I13: DISP OUT4)

In addition to the display set at I10: DISP OUT1,

displays can be set at I11: DISP OUT2, I12: DISP

OUT3, and I13: DISP OUT4 for cyclic display in the

order of the parameter number.

c. User Setting of Engineering Unit and Scale

(I30: ENGR.UNIT, I31: EASY EU SET, I33:

ENGR.LRV, and I34: ENGR.URV)

These parameters allow the entry of the

engineering units and scale to be displayed.

The engineering unit can be selected from the

parameter I31: EASY EU SET as listed below.

Alternately, up to eight alphanumerics, spaces, and

a slash “/” can be input on keypad at I30: ENGR.

UNIT; only first six are displayed on the integral

indicator.
Select the unit from the list of I31: EASY EU SET.

kPa

MPa

mbar

bar

psi

psia

mmH2O

mmHg

mmHgA

mmAq

mmWG

Torr

inH2O

inHg

inHgA

ftH2O

gf/cm2

kgf/cm2

kg/cm2G

kg/cm2A

atm

kg/h

t/h

m3/h

m3/min

l/h

l/min

kl/h

kl/min

Nl/h

Nl/min

Nm3/h

Nm3/min

ACFH

ACFM

SCFH

SCFM

GPH

GPM

m

mm

in

ft

kg/m3

g/cm3

Follow the procedure below to change the settings.

• Example: Set an engineering unit

M.

CODE

CAPS

CLR

ESC

SET

I30:ENGR.UNIT

M

FEED

NO

OK

SET

I30:ENGR.UNIT

M_

Set

M.

Press the key twice to
enter the setting.

Press the (OK) key.

F0322.ai

Note that following symbols are not available.

. – , + * ) ( ’ & % $ # ” !

The transmitter integral indicator shows

“-- -- -- -- -- --” when these are entered.

• Example: Set lower range value (LRV) to

–50

and upper range value (URV) to

50.

FEED

NO

OK

SET

I34:ENGR.URV

50 M

Press the (OK) key.

F0323.ai

DEL

CLR

ESC

DATA

DIAG

PRNT

ESC

PARAM

I32:ENGR.EXP

---

I33:ENGR.LRV

- 50 M

I34:ENGR.URV

50 M

DEL

CLR

ESC

SET

I33:ENGR.LRV

0.00 M

- 50

Set

–50.

Press the key twice to
enter the setting.

Setting LRV

Setting URV

Set

50.

Press the key twice to
enter the setting.

SET

I34:ENGR.URV

100.00 M

+ 50

FEED

NO

OK

SET

I33:ENGR.LRV

- 50 M

Press the (OK) key.