Yokogawa EJX115A User Manual

Page 35

Advertising
background image

<5. Parameter Summary>

5-3

IM 01C25T03-01E

No. Parameter name

Item

*

1

R/W

Content

Default value

Applicable

model

U

pl

oa

d

da

ta

F

P

L

G

ALARM SET

Alarm setting

G10 P AL MODE

Alert mode

W INHIBIT, HI. AL DETECT, LO.

AL DETECT, or HI/LO. AL

DETECT

INHIBIT

G11 P HI. AL VAL

High side alert value

W -32000 to 32000, unit

specified in C20

100.000 kPa

G12 P LO. AL VAL

Low side alert value

W -32000 to 32000, unit

specified in C20

-100.000 kPa

G20 SP AL MODE

Static pressure alert mode

W INHIBIT, HI. AL DETECT, LO.

AL DETECT, or HI/LO. AL

DETECT

INHIBIT

— 

G21 SP HI. AL VAL

High side alert value of SP*

2

W -32000 to 32000, unit

specified in D30

— 

G22 SP LO. AL VAL

Low side alert value of SP

W -32000 to 32000, unit

specified in D30

0.00000 MPa

— 

G30 T AL MODE

Temperature alert mode

W INHIBIT, HI. AL DETECT, LO.

AL DETECT, or HI/LO. AL

DETECT

INHIBIT

G31 T HI. AL VAL

High side alert value of

temperature

W -50 to 130

120 degC

G32 T LO. AL VAL

Low side alert value of

temperature

W -50 to 130

-40 degC

G50 AUTO RECOVER Auto-recover from sensor error

W OFF or ON

ON

G60 SELF CHECK

Self-diagnostics

R

See A60

H

AUTO SET

Automatic setup

H10 AUTO P LRV

Lower range value auto setup

W -32000 to 32000, unit

specified in C20

As specified

H11 AUTO P URV

Upper range value auto setup

W -32000 to 32000, unit

specified in C20

As specified

H20 AUTO SP LRV

SP lower range value auto

setup

W -32000 to 32000, unit

specified in D30

0.00000 MPa

— 

H21 AUTO SP URV

SP upper range value auto

setup*

2

W -32000 to 32000, unit

specified in D30

— 

H60 SELF CHECK

Self-diagnostics

R

See A60

I

DISP SET

Display setting

I10

DISP OUT1

LCD output 1

W PRES, PRES %, ENGR.

PRES, SP, or SP %

PRES %

I11

DISP OUT2

LCD output 2

W PRES, PRES %, ENGR.

PRES, SP, SP %, or ---

---

I12

DISP OUT3

LCD output 3

W See I11

---

I13

DISP OUT4

LCD output 4

W See I11

---

I20

P DISP MODE

% display mode

W LINEAR or SQUARE ROOT

LINEAR

I21

PRES % RESO

% display resolution

W NORMAL or HIGH

RESOLUTION

NORMAL

I30

ENGR. UNIT

User set engineering unit

W 8 alphanumeric characters

I31

EASY EU SET

Engineering unit select

W

I32

ENGR. EXP

Exponents

W ---, Ч10, Ч100, Ч1000

---

I33

ENGR. LRV

User set lower range limit

W -32000 to 32000, unit

specified in I30

0.00

I34

ENGR. URV

User set upper range limit

W -32000 to 32000, unit

specified in I30

100.00

I35

ENGR. POINT

Decimal place of user set

W 0 to 4

1

I40

BAR INDICATR

Bar indicator

W OFF or ON

ON

I41

POWER ON INF

Display when powering on

W OFF or ON

ON

I60

SELF CHECK

Self-diagnostics

R

See A60

*1: R/W: R = Read only, W = Read & Write

*2:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.