<5. Parameter Summary>

5-2

IM 01C25T03-01E

No. Parameter name

Item

*

1

R/W

Content

Default value

Applicable

model

U

pl

oa

d

da

ta

F

P

L

D

AUX SET 1

Auxiliary setting data 1

D10 LOW CUT

Low cut

W 0.00 to 20.00%

10.00%

D11 LOW CUT MODE Low cut mode

W LINEAR or ZERO

LINEAR

D15 H/L SWAP

Impulse piping accessing

direction

W NORMAL or REVERSE

NORMAL

— 

D16 H2O UNIT SEL

H2O unit select

W @4degC or @20degC

(68.0F)

@4degC

D20 OUT LIMIT (L)

Low side output limiter

W -2.50 to 110.00%

-2.50%

D21 OUT LIMIT (H)

High side output limiter

W -2.50 to 110.00%

110%

D22 REV OUTPUT

Output reversal

W NORMAL or REVERSE

NORMAL

D25 BURNOUT

CPU error

R

HIGH or LOW

D26 ERROR OUT

Hardware error

W BURNOUT DIR or HOLD

BURNOUT DIR   

D30 SP UNIT

Static pressure unit

W See C20

MPa

— 

D31 SP A/G SLCT

Gauge/Abs select for static

pressure

W GAUGE or ABSOLUTE

ABSOLUTE

— 

D32 ATM. PRESS

Coefficient for given gauge

pressure

W Unit specified in D30

0.10133 MPa

— 

D33 SP LRV

Lower limit of static pressure

W -32000 to 32000 within

measurement range

0.0 MPa

— 

D34 SP URV

Upper limit of static pressure*

2

W -32000 to 32000 within

measurement range

— 

D35 SP POINT

Decimal place of static

pressure

W 0 to 4

1

— 

D36 SP DAMPING

Damping time constant of SP

W 0.00 to 100.00 seconds

2.00 seconds

— 

D37 SP SELECT

H/L select for static pressure

W HIGH or LOW

HIGH

— 

D40 TEMP UNIT

Temperature setting unit

W degC, degF, or K

degC

D50 QUICK RESP

Quick response

W OFF or ON (enable 0.00 to

0.50 seconds at C30)

OFF

D55 WRT PROTECT

Write protect indicator

R

NO or YES

NO

D56 WRT ENABLE

Write protect release

W 8 alphanumeric characters

None

D57 NEW PASSWORD User set password for write

protect

W 8 alphanumeric characters

None

D58 SOFTWR SEAL

Software seal

R

BREAK or KEEP

KEEP

D60 SELF CHECK

Self-diagnostics

R

See A60

E

AUX SET 2

Auxiliary setting data 2

E10 T. ZERO CMP

Temperature compensation

mode

W OFF or ON

OFF

E11 TEMP ZERO

Zero shift compensation

W -99.999 to 99.999%/degC

0.000%/degC

E30 BI DIRE MODE

Bidirectional mode

W OFF or ON

OFF

E50 DO SELECT

Contact output select

W INHIBIT, PRES, SP, TEMP,

PRES/SP, PRES/TEMP, SP/

TEMP, or PRES/SP/TEMP

INHIBIT

E51 DO SIG. TYPE

Signal type select

W OFF WHEN ALARM or ON

WHEN ALARM

ON WHEN

ALARM

E52 D OUTPUT

Contact output

R

OFF or ON

OFF

E60 SELF CHECK

Self-diagnostics

R

See A60

*1: R/W: R = Read only, W = Read & Write

*2:

The default value shows MWP (Maximum working pressure) of the capsule.