3.2.3 Setting Parameters

Set or change the parameters as necessary. After

completing these, do not fail to use the “DIAG” key

to confirm that “GOOD” is displayed for the self-

diagnostic result at

_60: SELF CHECK.

(1) Tag No. Setup

(C10: TAG NO)

Use the procedure below to change the Tag No. Up

to 16 alphanumeric characters can be entered.

Press the key to turn on

the BT200.

Connect the transmitter and

BT200 using a communication

cable and press the

key.

PARAM

01:MODEL

EJX110 M

02:TAG NO.

YOKOGAWA

03:SELF CHECK

GOOD

OK

MENU

A:DISPLAY

B:SENSOR TYPE

C:BASIC SETUP

D:AUX SET1

E:AUX SET2

G:ALARM SET

HOME

SET

ADJ

ESC

MENU

C:BASIC SETUP

D:AUX SET 1

E:AUX SET 2

G:ALARM SET

H:AUTO SET

I:DISP SET

HOME

SET

ADJ

ESC

MENU

C10:TAG NO.

YOKOGAWA

C20:PRES UNIT

kPa

C21:PRES LRV

0.00000 kPa

DATA

DIAG

PRNT

ESC

<When power is off>

Select C: BASIC SETUP and

press the key.

Select C10: TAG NO. and press

the key.

Displays the model name of

connected transmitter, TAG NO. and

diagnostics information. Press the

(OK) key after confirmation.

Press the (SET) key to

display the SET menu panel.

--WELCOME--

BRAIN TERMINAL

ID: BT200
check connection

push ENTER key

UTIL

FEED

F0311_1.ai

SET

C10:TAG NO.

YOKOGAWA

YOKOGAWA

CODE

CAPS

CLR

ESC

When you have made an entry mistake, return

the cursor using the key, then reenter.

Set the new TAG NO. (FIC-1a).

FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1aWA
FIC-1a

Set TAG NO. and press the

key.

SET

C10:TAG NO.

YOKOGAWA

FIC-1a _

CODE

caps

CLR

ESC

• Example: Set a Tag No. to FIC-1a

SET

C10:TAG NO.

FIC-1a

FEED

NO

OK

DATA

DIAG

PRNT

ESC

This is the panel for confirming
set data. The set data items flash.
When all items have been
confirmed, press the
again. (To go back to the setting
panel, press the (NO) key.

SET

C10:TAG NO.

YOKOGAWA

FIC-1a
print off

F2:printer on

PARAM

C10:TAG NO.

FIC-1a

C20:PRES UNIT

kPa

C21:PRES LRV

0.00000 kPa

FEED

POFF

NO

The DPharp TAG NO. was
overwritten.
Press the (OK) key to
return to the parameter panel.
Press the (NO) key to
return to the setting panel.

F0311_2.ai

(2) Calibration Range Setup

a. Setting Calibration Range Unit

(C20: PRES UNIT)

The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

• Example: Change the unit from

mmH2O to kPa.

ESC

SET

C20:PRES UNIT

kPa

FEED

NO

OK

SET

C20:PRES UNIT

mmH2O

< mmWG >

< mmHg >

< Torr >

< kPa >

Use the or
key to select

kPa.

Press the key twice
to enter the setting.

Press the (OK) key.

F0312.ai

Note that the Yokogawa default setting for the

standard temperature is 4°C (39.2°F). For the

units of mmH

2

O, mmAq, mmWG, inH

2

O, and

ftH

2

O, the pressure varies according to the

standard temperature definition. When a standard

temperature of 20°C (68°F) is required, select

@20degC (68.0F) at the parameter D16:H2O UNIT

SEL.
Available pressure units are shown below.

mmH2O

mmAq

mmWG

mmHg

Torr

kPa

MPa

mbar

bar

gf/cm2

kgf/cm2

inH2O

inHg

ftH2O

psi

atm

Pa

hPa

Advertising