5) output signal low cut mode setup – Yokogawa EJX115A User Manual

Page 16

Advertising
background image

<3. Operation>

3-8

IM 01C25T03-01E

(4) Output Mode and Integral Indicator

Display Mode Setup
(C40: OUTPUT MODE, I20: P DISP

MODE)

The mode setting for the output signal and the

integral indicator can be performed independently.
This mode is set as specified in the order when the

instrument is shipped. Follow the procedure below

to change the mode.
If the instrument is equipped with an integral

indicator and the display mode is

SQUARE ROOT,

“ ” is displayed on the integral indicator.

• Output mode for 4-20 mA output

• Example: Set output mode from

Linear to

Square root.

ESC

SET

C40:OUTPUT MODE

SQUARE ROOT

FEED

NO

OK

SET

C40:OUTPUT MODE

LINEAR

< LINEAR >

< SQUARE ROOT >

Use the or key
to select

SQUARE ROOT.

Press the key twice to
enter the setting.

Press the (OK) key.

F0316.ai

• Integral indicator display mode

• Example: Set display mode from

Linear to

Square root.

ESC

SET

I20:P DISP MODE

SQUARE ROOT

FEED

NO

OK

SET

I20:P DISP MODE

LINEAR

< LINEAR >

< SQUARE ROOT >

Use the or key
to select

SQUARE ROOT.

Press the key twice to
enter the setting.

Press the (OK) key.

F0317.ai

(5) Output Signal Low Cut Mode Setup

(D10: LOW CUT, D11: LOW CUT MODE)

Low cut mode can be used to stabilize the output

signal near the zero point. The low cut point can

be set in a range from 0 to 20%, the direct ratio

corresponding to the output signal of 4 to 20 mA.

(Hysteresis: ±10% of the cut point)
Either

LINEAR or ZERO can be selected as the low

cut mode. Unless otherwise specified, the cut mode

is set to LINEAR at the factory.
Note that when the output modes of the output

signal and the integral indicator are selected as

SQUARE ROOT and LINEAR accordingly, the low

cut function is not available for the integral indicator

display.

• Example: Change the low cut setting range

from 10% to 20%, and the low

cut mode from

LINEAR to ZERO in

the SQUARE ROOT output mode.

FEED

NO

OK

SET

D11:LOW CUT MODE

ZERO

Use the or key
to select

ZERO.

Press the key twice to
enter the setting.
Press the (OK) key.

F0318.ai

FEED

NO

OK

SET

D10:LOW CUT

20.00 %

ESC

SET

D11:LOW CUT MODE

LINEAR

< LINEAR >

< ZERO >

DATA

DIAG

PRNT

ESC

PARAM

D10:LOW CUT

20.0 %

D11:LOW CUT MODE

ZERO

D15:H/L SWAP

NORMAL

CLR

ESC

SET

D10:LOW CUT

10.00 %

+ 20.00

Set

20.

Press the key twice to
enter the setting.

Press the (OK) key.
Next, the [D11: LOW CUT MODE]
setting panel is displayed.

(%)

50

20

0

50 (%)

Output

● Low cut mode “LINEAR”

Input

(%)

50

20

0

50 (%)

● Low cut mode “ZERO”

LOW CUT at 20%

Input

Advertising