11) software write protect, 11) software write protect -12 – Yokogawa EJX115A User Manual

Page 20

Advertising
background image

<3. Operation>

3-12

IM 01C25T03-01E

Standard specifications
The burnout direction switch is set to HIGH. If a

failure occurs, the transmitter outputs a 110% or

higher signal.

Option code /C1
The burnout direction switch is set to LOW. If a

failure occurs, a –5% or lower output is generated.

• Example: Standard specifications

Slide switch position: H

D25: BURNOUT

HIGH

F0328.ai

• Example: Option code /C1

Slide switch position: L

D25: BURNOUT

LOW

(11) Software Write Protect

(D55: WRT PROTECT, D56: WRT

ENABLE, D57: NEW PASSWORD)

Transmitter configured data can be saved by the

write protect function. Write protect status (D55:

WRT PROTECT) is set from

NO to YES when eight

alphanumerics are entered in the parameter D57:

NEW PASSWORD. Accordingly, the transmitter

does not accept any parameter changes. When

the eight alphanumeric password is entered in the

parameter D56: WRT ENABLE, the transmitter

accepts parameter changes during a 10 minute

period.
To cancel the transmitter for the software write

protection completely, use D56: WRT ENABLE to

first release the write protect function and then enter

eight spaces in the D57: NEW PASSWORD field.
The software write protection does not affect the

function of external zero adjustment screw.
To disable the external zero adjustment screw, set

the parameter J15: EXT ZERO ADJ to INHIBIT

before activating the software write protection.

a. Setting Password (D57: NEW PASSWORD)

Enter

1234ABCD.

Then status of parameter D55:

WRT PROTECT becomes YES.

F0329.ai

• Example: Set the password to 1234ABCD.

SET

D57:NEW PASSWORD

1234ABCD

CODE

CAPS

CLR

ESC

SET

D57:NEW PASSWORD

1234ABCD

FEED

NO

OK

Press the key twice
to enter the setting.

Press the (OK) key.

b. Entering Password to Enable Parameter

Change (D56: WRT ENABLE)

Enter the password.

Parameter changes are available

for 10 minutes.

F0330.ai

• Example: Enter the password of 1234ABCD.

SET

D56:WRT ENABLE

1234ABCD

CODE

CAPS

CLR

ESC

SET

D56:WRT ENABLE

PASS

FEED

NO

OK

Press the key twice
to enter the setting.

Press the (OK) key.

c. Releasing Password

(D57: NEW PASSWORD)

To release the password, enter eight spaces at

D57: NEW PASSWORD during the period that the

parameter change is possible.

d. Software Seal (D58: SOFTWR SEAL)

When you lose the password that has been

registered, it is possible to release the write protect

function by using general password. Contact

Yokogawa about the general password. When

the password is used, the status shown in the

parameter D58: SOFTWR SEAL is changed from

KEEP to BREAK. The status returns to KEEP

by entering a newly set password at D56: WRT

ENABLE.