13) bi-directional flow measurement setup, 14) range change while applying actual inputs – Yokogawa EJX115A User Manual

Page 21

Advertising
background image

<3. Operation>

3-13

IM 01C25T03-01E

(12) Output Status Setup when a Hardware

Error Occurs
(D26: ERROR OUT)

This parameter allows the setting of the output

status when a hardware error occurs. The following

selections are available.
(a) BURNOUT DIR; Outputs the corresponding

values of 110% or –5% of output signals

according to the setting by burnout direction

switch (BO) on the CPU board.

(b) HOLD; Outputs the last value held before the

error occurred.

Note: A hardware error means CAP.ERR of AL.01 or AMP.ERR

of AL.02 which are shown in table 4.1 Alarm Message

Summary.

• Example: Set the output status to

HOLD when

a hardware error occurs.

ESC

SET

D26:ERROR OUT

BURNOUT DIR

< BURNOUT DIR >

< HOLD >

Use the or key
to select

HOLD.

Press the key twice to
enter the setting.

F0331.ai

Then press the (OK) key.

(13) Bi-directional Flow Measurement

Setup
(E30: BI DIRE MODE)

(a) This parameter enables selection of 50% output

at an input of 0 kPa.

Procedure is shown in the figure below.

(b) Combining this with

C40: OUTPUT MODE

provides a square root output computed

independently for 0% to 50% output and for

50% to 100% output.

• Example: If measurement range is 0 to 10 kPa

(LRV=0 kPa, URV=10 kPa)

The measurement range changes to –10 to 0 to 10 kPa
(output 0% to 50% to 100).
Note that

C21: PRES LRV and C22: PRES URV

are not changed.

ESC

SET

E30:BI DIRE MODE

OFF

< OFF >

< ON >

Use the or key
to select

ON.

Press the key twice to
enter the setting.

F0332.ai

Then press the (OK) key.

20 mA (100% display)

4 mA (–100% display)

● Output mode “LINEAR”

LRV

HRV

F0333.ai

20 mA (100% display)

Low Cut

4 mA (–100% display)

● Output mode “SQUARE ROOT”

LRV

HRV

(14) Range Change while Applying Actual

Inputs
(H10: AUTO P LRV, H11: AUTO P URV)

This feature allows the lower and upper range

values to be set up automatically with the actual

input applied. If the lower and upper range values

are set, C21: PRES LRV and C22: PRES URV are

changed at the same time.
Follow the procedure in the figure below.

The measurement span is determined by the upper

and lower range values. Changing the lower range

value results in the upper range value changing

automatically, keeping the span constant.

• Example 1: When changing the lower range

value to 0.5 kPa for the present

setting of 0 to 30 kPa, take the

following action with input pressure

of 0.5 kPa applied.

FEED

NO

OK

SET

H10:AUTO P LRV

0.5000 kPa

DATA

DIAG

PRNT

ESC

PARAM

H10:AUTO P LRV

0.5000 kPa

H11:AUTO P URV

30.500 kPa

H20:AUTO SP LRV

0.0 MPa

ESC

SET

H10:AUTO P LRV

0 kPa

+ 0

F0334.ai

The upper range value is changed
keeping the span constant.
Parameters

C21 and C22 are

changed at the same time.

Press the key twice.
The lower range value is changed
to 0.5 kPa.

Press the (OK) key.