<3. Operation>

3-17

IM 01C25T03-01E

c. Sensor Trim for Static Pressure

(J21: SP ZERO ADJ, J22: SP SPAN ADJ,

J25: SP ZERO DEV, J26: SP SPAN DEV)

For the transmitters (Except for EJX120A/EJA120E),

zeroing and full sensor trim of the static pressure

is performed in the same way as with the primary

process variable (PV). Note that the static pressure

sensor trim should be done only after trimming

the PV.

d. Reset Trim Adjustment to Factory Setting

(J56: CLEAR ADJ)

Use

PRES or SP of J56: CLEAR ADJ parameter

to reset the trim adjustment to the initial calibrated

values that were set. When

PRES is selected to

clear the adjustment, the amount of the adjustment

by the external zero-adjustment screw is returned to

the initial setting as well.

• Example: Reset the trim adjustment of pressure

to factory set characterization curve.

ESC

SET

J56:CLEAR ADJ

---

FEED

NO

OK

Use the or key
to select

PRES.

Press the key twice to
enter the setting.

Press the (OK) key.

F0342.ai

SET

J56:CLEAR ADJ

---

< --- >

< PRES >

< SP >

< 4-20mA >

(16) Test Output Setup

(K10: OUTPUT X %)

This feature can be used to output a fixed current

for loop checks. The available range for test output

depends on the setting at parameters D20: OUT

LIMIT (L) and D21: OUT LIMIT (H), whose limit is

from 3.6 mA (–2.5%) to 21.6 mA (110%).

• Example: Output 12 mA (50%) fixed current.

CLR

ESC

SET

K10:OUTPUT X %

50.00% ACTIVE

FEED

NO

OK

SET

K10:OUTPUT X %

0.00 %

+ 050.00

Set

50.00%.

Press the key twice to
output a fixed current at 50%.

ACTIVE is displayed while this is
being executed.
Press the (OK) key to cancel
the fixed current output.

F0343.ai

NOTE

• Fixed current output and DO Test continue

for a given holding time, then is released

automatically. Even if the BT200 power

supply is turned off or the communication

cable is disconnected, the test output will

continue for that time.

The holding time can be selected from 10

min*, 30 min, 60 min, 3 hour, 6 hour or 12

hour by the parameter K45: TEST TIME.

*: Default value.

• Press the

(OK) key to release test output

immediately.

(17) Signal Characterizer

This function is used to compensate the output

for non-linear applications. The characterized

values are applied to the 4-20 mA output. For

the measured pressure, a maximum of nine

coordinates can be specified between 0-100%.

Perform the coordinate settings while the T10: S. C.

ENABLE parameter is

INHIBIT.

To apply the settings to the output, set the T10: S.

C. ENABLE parameter to

ENABLE.

Note that the transmitter rejects the activation of the

function by AL. 60 with the following transmitter’s

status:

• When the specified coordinates of x and y are

not incremental as the input increases.

• When the output mode of the output signal is

set as

SQUARE ROOT; at the same time, the

low cut mode is set to

LINEAR.

F0344.ai

Y

X

100%

0%

100%

INPUT

OUTPUT

Input pressure in %

Characterized value