18) process alarm, 19) status output (option code al), Caution – Yokogawa EJX115A User Manual

Page 26: Example: set the signal characterizer enable

Advertising
background image

<3. Operation>

3-18

IM 01C25T03-01E

• Example: Set the number of coodinates on the

line graph to 5.

ESC

CLR

SET

T11:NUM OF POINT

5

FEED

NO

OK

SET

T11:NUM OF POINT

9

5

F0345.ai

Set

5.

Press the key twice to
enter the setting.

Press the (OK) key.

• Example: Set the first coordinates (X1, Y1) as

(12, 14) in %.

ESC

CLR

SET

T23:Y1

10.00%

+ 014.00

CLR

ESC

SET

T22:X1

10.00%

+ 012.00

F0346.ai

PARAM

T21:Y

0.00%

T22:X1

12.00%

T23:Y1

14.00%

PRNT

DATA DIAG

ESC

Set

12 for X1.

Press the key twice to
enter the setting.
Press the (OK) key.

Set

14 for Y1.

Press the key twice to
enter the setting.
Press the (OK) key.

• Example: Set the signal characterizer

ENABLE.

ESC

SET

T10:S.C.ENABLE

ENABLE

FEED

NO

OK

SET

T10:S.C.ENABLE

INHIBIT

< INHIBIT>

< ENABLE >

F0347.ai

Use the or key
to select

ENABLE.

Press the key twice to
activate the function.

Press the (OK) key.

(18) Process Alarm

(G10: P AL MODE, G11: P HI.AL VAL,

G12: P LO.AL.VAL)

The function is used to display the alarm codes

when the input pressure exceeds the specified

value within the calibration range. The same is

available for the input static pressure and the

capsule temperature on the pressure sensor.

Refer to table 4.1 Alarm Message Summary for the

specific alarm code to be generated.

• Example: Set alarm mode from

OFF to HI.AL

DETECT.

ESC

SET

G10:P AL MODE

HI.AL DETECT

FEED

NO

ESC

SET

G10:P AL MODE

INHIBIT

< INHIBIT >

< HI.AL DETECT >

< LO.AL DETECT >

< HI/LO.AL DETECT >

Use the or key
to select

HI. AL DETECT.

Press the key twice to
enter the setting.

Press the (OK) key.

Alarm code is generated when the
output goes beyond the value set
at G11: P HI. AL VAL.

F0348.ai

• Example: Set the higher alert value of 75 for

alarm generation.

CODE

CAPS

CLR

ESC

SET

G11:P HI.AL VAL

75.0000 kPa

FEED

NO

OK

SET

G11:P HI.AL VAL

100.000 kPa

+ 75

Set

75.

Press the key twice to
enter the setting.

Press the (OK) key.

Then the alarm code “AL.35 P. HI”
is generated when the input
pressure goes beyond that value.

F0349.ai

(19) Status Output (option code AL)

This feature is used for a transistor output (open

collector) of an on/off signal according to the

status of high and low alarm limits, which are

user-configurable values as shown in (18) Process

Alarm. The status output can be assigned as

any combination of the high or low limits of the

input pressure, input static pressure, or capsule

temperature.

CAUTION

Execute DO testing by the parameter "K40:

DO test" whenever turning on the transmitter

or detecting the short interruption in order to

check that the alarm contact output is correctly

configured.

NOTE

No status output signal has been defined for a

CPU failure or hardware error. Use a 4-20 mA

signal to indicate a transmitter’s failure.