<4. Self-diagnostics>

4-2

IM 01C25T03-01E

4.1.2 Checking with Integral Indicator

NOTE

If an error is detected by running self-diagnostics,

an error number is displayed on the integral

indicator. If there is more than one error, the error

number changes at three-second intervals.

See table 4.1 regarding the alarm codes.

F0404.ai

Figure 4.1

Integral Indicator

4.2 Alarms and Countermeasures

Table 4.1

Alarm Message Summary

Indicator

BT200 display

Cause

Output operation

during error

Countermeasure

None

GOOD

AL. 01

CAP. ERR

01: P-SENSOR ERR

Sensor problem.

Outputs the signal

(Hi or Low) set with

parameter D26.

[Status output:

undefined]

Replace capsule when

error keep appearing

error even after restart.

01: CT-SENSOR ERR Capsule temperature sensor

problem.

Replace capsule.

01: C-EEPROM ERR Capsule EEPROM problem.

AL. 02

AMP. ERR

02: AT-SENSOR ERR Amplifier temperature sensor

problem.

Replace amplifier.

02: A-EEPROM ERR Amplifier EEPROM problem.
02: CPU BOARD ERR Amplifier problem.

AL. 10

PRESS

10: P OVER SPEC

Input is outside measurement

range limit of capsule.

Outputs upper range

limit (URL) or lower

range limit (LRL).

Check input or

replace capsule when

necessary.

AL. 11

ST. PRSS

11: SP OVER SPEC

Static pressure exceeds limit.

Continues to operate

and output.

AL. 12

CAP. TMP

12: CT OVER SPEC

Capsule temperature is outside

range (–50 to 130°C).

Use heat insulation or

make lagging to keep

temperature within

range.

AL. 13

AMP. TMP

13: AT OVER SPEC

Amplifier temperature is outside

range (–50 to 95°C).

AL. 30

RANGE

30: P OVER RANGE

Output is outside upper or

lower range limit value.

Outputs upper range

value (URV) or lower

range value (LRV).

Check input and range

setting, and change

them as needed.

AL. 31

SP. RNG

31: SP OVER RANGE Static pressure exceeds

specified range.

Continues to operate

and output.

AL. 35

P. HI

35: P HIGH ALARM

Input pressure exceeds

specified threshold.

Check input.

AL. 36

P. LO

36: P LOW ALARM

AL. 37

SP. HI

37: SP HIGH ALARM Input static pressure exceeds

specified threshold.

AL. 38

SP. LO

38: SP LOW ALARM

AL. 39

TMP. HI

39: CT HIGH ALARM Detected temperature exceeds

specified threshold.

Check capsule

temperature.

AL. 40

TMP. LO

40: CT LOW ALARM