<5. Parameter Summary>

5-1

IM 01C25T03-01E

5. Parameter Summary

Instruments to which applicable:

F: Differential pressure transmitters

P: Absolute and gauge pressure transmitters

L: Flange mounted differential pressure transmitters

No. Parameter name

Item

*

1

R/W

Content

Default value

Applicable

model

U

pl

oa

d

da

ta

F

P

L

01

MODEL

Model

R

EJX (for EJX series)

EJA (for EJA series)

02

TAG No.

Tag number

R

As specified

03

SELF CHECK

Self-diagnostics

R

GOOD

A

DISPLAY

Measured data display

A10 OUTPUT

Output (in %)

R

-2.5 to 110%

A11 PRES

Measured pressure after zero

adjustment

R

Unit specified in C20

A15 OUTPUT mA

Output current

R

3.600 to 21.600 mA

A16 ENGR. OUTPUT

User scaled value

R

Unit specified in I30

A17 ENGR. EXP

Exponents

R

Unit specified in I32

A20 SP %

Static pressure (in %)

R

-10 to 110%

— 

A21 SP

Static pressure after zero

adjustment

R

Unit specified in D30

— 

A30 CAPSULE TEMP

Capsule temperature

R

Unit specified in D40

A60 SELF CHECK

Self-diagnostics

R

Refer to Table 4.1 Alarm

Message Summary

B

SENSOR TYPE

Sensor type

B10 MODEL

Model and capsule type

R

Model and capsule type

B11 STYLE NO.

Style number

R

Style number of product

B20 PRES LRL

Lower range limit

R

Unit specified in C20

B21 PRES URL

Upper range limit

R

Unit specified in C20

B22 P MIN SPAN

Minimum span

R

Unit specified in C20

B30 SP LRL

Lower range limit for static

pressure

R

Unit specified in D30

— 

B31 SP URL

Upper range limit for static

pressure

R

Unit specified in D30

— 

B32 SP MIN SPAN

Minimum span for static

pressure

R

Unit specified in D30

— 

B60 SELF CHECK

Self-diagnostics

R

See A60

C

BASIC SETUP

Setting data

C10 TAG NO.

Tag number

W 16 alphanumeric characters

As specified

C20 PRES UNIT

Measurement range unit

W mmH

2

O, mmAq, mmWG,

mmHg, Torr, kPa, MPa, mbar,

bar, gf/cm

2

, kgf/cm

2

, inH

2

O,

inHg, ftH

2

O, psi, atm, Pa, hPa

kPa

C21 PRES LRV

Lower range value

W -32000 to 32000 within

measurement range

As specified

C22 PRES URV

Upper range value

W -32000 to 32000 within

measurement range

As specified

C23 PRES POINT

Decimal place

W 0 to 4

2

C30 AMP DAMPING

Damping time constant at

amplifier

W 0.50(0.00) to 100.00 seconds,

see D50

2.00 seconds or

as specified

C40 OUTPUT MODE

Output mode

W LINEAR or SUQARE ROOT

LINEAR or as

specified

C60 SELF CHECK

Self-diagnostics

R

See A60

*1: R/W: R = Read only, W = Read & Write

*2:

The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.