<6. Wiring>

6-3

IM 01C25B01-01E

(2) Flameproof Type
Wire cables through a flameproof packing adapter,

or use a flameproof metal conduit.
■ Wiring cable through flameproof packing

adapter.

• Apply a non-hardening sealant to the terminal

box connection port and to the threads on the

flameproof packing adapter for waterproofing.

Flameproof packing

adapter

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

F0609.ai

Figure 6.9

Typical Cable Wiring Using Flameproof

Packing Adapter

■ Flameproof metal conduit wiring

• A seal fitting must be installed near the terminal

box connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of

the terminal box connection port, flexible metal

conduit and seal fitting for waterproofing.

F0610.ai

Non-hazardous area

Hazardous area
Flameproof

heavy-gauge

steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Flameproof flexible

metal conduit

Apply a non-hardening

sealant to the threads of

these fittings for

waterproofing

After wiring, impregnate the fitting

with a compound to seal tubing.

Figure 6.10 Typical Wiring Using Flameproof Metal

Conduit

6.5 Grounding

Grounding is always required for the proper

operation of transmitters. Follow the domestic

electrical requirements as regulated in each

country. For a transmitter with a built-in lightning

protector, grounding should satisfy ground

resistance of 10Ω or less.
Ground terminals are located on the inside and

outside of the terminal box. Either of these terminals

may be used.

Ground terminal

(inside)

Ground terminal

(outside)

F0611.ai

SUPPL

Y

PULSE

CHECK

ALARM

Figure 6.11 Ground Terminals

6.6 Power Supply Voltage and

Load Resistance

When configuring the loop, make sure that the

external load resistance is within the range in the

figure below.

(Note) In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

600

250

0

10.5 16.6

25.2

42

External

load

resistance

R (Ω)

Power supply voltage E (V DC)

F0612.ai

Communication

applicable range

BRAIN and HART

R= E–10.5

0.0244

Figure 6.12 Relationship between Power Supply

Voltage and External Load Resistance