3 starting operation, 4 shutting down operation, 1 determining the differential pressure range – Yokogawa EJA115 User Manual

Page 33: Starting operation -3, Shutting down operation -3, Transmitter measurement range -3, Determining the differential pressure range -3

Advertising
background image

IM 01C22K01-01E

7-3

7. OPERATION

7.3 Starting Operation

After completing the zero point adjustment, follow the
procedure below to start operation.

1) Open the stop valve on the upstream side.
2) Gradually open the stop valve on the downstream

side. This places the transmitter in an operational
condition.

3) Confirm the operating status. If the output signal

exhibits wide fluctuations (hunting) due to periodic
variation in the process pressure, use BT200 to
dampen the transmitter output signal. Confirm the
hunting using a receiving instrument or the integral
indicator, and set the optimum damping time
constant. See Subsection 8.3.3 (3), “Damping Time
Constant Setup.”

4) After confirming the operating status, perform the

following.

IMPORTANT

• Remove the BT200 from the terminal box, and

confirm that none of the terminal screws are
loosened.

• Close the terminal box cover and the amplifier

cover. Screw each cover in tightly until it will
not turn further.

• Two covers are required to be locked on the

CENELEC, IECEx, and TIIS Flameproof type
transmitters. An Allen head bolts (shrouding
bolts) are provided under edge of the each
cover for locking. When a shrouding bolts are
driven counterclockwise by an Allen wrench, it
is coming out and locks up a cover. (See page
9-3) After locking, the covers should be
confirmed not to be opened.

• Tighten the zero-adjustment cover mounting

screw to fix the cover in position.

7.4 Shutting Down Operation

Shut down the transmitter operation as follows.
1) Turn off the power.
2) Close the stop valves on the up and downstream

sides.

NOTE

Whenever shutting down the transmitter for a
long period, remove any process fluid from the
transmitter pressure-detector section.

7.5 Transmitter Measurement

Range (Determining Differen-
tial Pressure Range)

The following describes the procedure for calculating
the differential pressure range and the calculation
example in low flow measurement.

Conversion factor in pressure unit:

1 Pa=1.01972

ϫ10

-1

mmH

2

O

1 mmH

2

O=9.80665 Pa

1 atm=1.01325

ϫ10

2

kPa

7.5.1

Determining the Differential Pres-

sure Range

Use the following procedures to determine a differential
pressure range according to the fluid conditions being
measured.

(a) Calculate a water or air equivalent flow from the

flow of the fluid being measured (100% flow).

᭿ Equivalent Water Flow Calculation

Q

w

= 0.03162 . Qf .

␳f

(1)

Where, Qw: Water equivalent volumetric flow (m

3

/h) at

4

°C, 1 atm

Qf: Volumetric liquid flow (m

3

/h) at operating

conditions (t

°C, p kPa)

␳f: Specific liquid density (kg/m

3

) at operating

conditions (t

°C, p kPa)

Advertising