Yokogawa EJA115 User Manual

Page 69

Advertising
background image

IM 01C22K01-01E

10-5

10. GENERAL SPECIFICATIONS

Item

Description

Code

CSA Explosionproof Approval

*1

Certificate: 1089598

Explosionproof for Class I, Division 1, Groups B, C and D

Dustignitionproof for Class II/III, Division 1, Groups E, F and G

Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x

Max. Process Temp.: T4; 120

ЊC (248ЊF), T5; 100ЊC (212ЊF), T6; 85ЊC (185ЊF)

Amb. Temp.: –40 to 80

ЊC (–40 to 176ЊF)

Process Sealing Certification

Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01

No additional sealing required. Primary seal failure annunciation: at the zero adjustment

screw

CF1

Canadian Standards
Association (CSA)

CSA Intrinsically safe Approval

*1

Certificate: 1053843

Intrinsically Safe for Class I, Groups A, B, C and D Class II and III, Groups E, F and G

Nonincendive for Class I, Division 2, Groups A, B, C and D Class II, Division 2,

Groups F and G and Class III (not use Safety Barrier)

Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60

ЊC (–40 to 140ЊF)

Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730

␮H

Process Sealing Certification

Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01

No additional sealing required. Primary seal failure annunciation: at the zero adjustment

screw

CS1

IECEx
Scheme

Attached flameproof
packing adapter

TIIS certification

SU2

G12

JS3

G11

JF3

IECEx Intrinsically safe, type n and Flameproof Approval

*2

Intrinsically safe and type n

Certificate: IECEx KEM 06.0007X

Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67

Amb. Temp.: –40 to 60

ЊC (–40 to 140ЊF), Max. Process Temp.: 120ЊC (248ЊF)

Electrical Parameters: [Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730

␮H

[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730

␮H

Flameproof

Certificate: IECEx KEM 06.0005

Ex d IIC T6...T4 Enclosure: IP67

Max.Process Temp.: T4;120

ЊC (248ЊF), T5;100ЊC (212ЊF), T6; 85ЊC (185ЊF)

Amb.Temp.: –40 to 75

ЊC (–40 to 167ЊF) for T4, –40 to 80ЊC (–40 to 176ЊF) for T5,

–40 to 75

ЊC (–40 to 167ЊF) for T6

CU1

Combined CF1 and CS1

*1

TIIS Flameproof Approval, Ex do IIC T4X

Certificate: C15296 (Without integral indicator)

C15297 (With integral indicator)

Amb. Temp.: –20 to 60

ЊC, Process Temp.: –20 to 120ЊC

TIIS Intrinsically safe Approval, Ex ia IIC T4

Certificate: C14632

Amb. Temp.: –20 to 60

ЊC, Process Temp.: –20 to 120ЊC

Electrical connection: G1/2 female
Applicable cable: O. D. 8 to 12 mm

1 pc.
2 pcs.

T1005-2.EPS

*1:

Applicable for Electrical connection code 2 and 7 (1/2 NPT female).

*2:

Applicable for Electrical connection code 2, 4 and 7 (1/2 NPT and M20 female).

Advertising