IM 01C22K01-01E

8-10

8. BRAIN TERMINAL BT200 OPERATION

(7) Integral Indicator Scale Setup

The following 5 displays are available for integral
indicators.

T0809.EPS

D20: DISP SELECT

and Display

NORMAL %

USER SET

USER & %

INP PRES

PRES & %

Indicates –5 to 110% range
depending on the Measurement
range (C21, C22).

Indicates values depending on the
Engineering range (D22, D23).

(

Note 1

)

Units set using Engineering unit
(D21) are not indicated.

Indicates user set and % alternately
in 3 second intervals.

Indicates input pressure.

(

Note 2

)

Indication limits –19999 to 19999.

Indicates input pressure and %
alternately in 3 second intervals.

A10:OUTPUT (%)

45.6 %

Description

and Related parameters

A11:ENGR.OUTPUT

20.0 M

A10:OUTPUT (%)

45.6 %

A11:ENGR. OUTPUT

20.0 M

A40:INPUT

456 kPa

A10:OUTPUT (%)

45.6 %

A40:INPUT

456 kPa

(Note 1) Scale range can be specified with range limit specifications up

to 5 digits (excluding any decimal point) for low or high range

limits within the range of –19999 to 19999.

The range with decimals is available to the third decimal place.

(Note 2) It indicates the value after zeroing.

See (a.) through (c.) for each setting procedure.

• Example: Change the low cut setting range

from 10% to 20%, and the low
cut mode from LINEAR to ZERO.

FEED

NO

OK

SET
D11:LOW CUT MODE
ZERO

Use the or key

to select “ZERO.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0818.EPS

FEED

NO

OK

SET
D10:LOW CUT
20.0 %

ESC

SET
D11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >

DATA

DIAG

PRNT

ESC

PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D20:DISP SELECT
NORMAL %

CLR

ESC

SET
D10:LOW CUT
10.0 %
+ 20.0

Set “20.”

Press the key twice to

enter the setting.

Press the (OK) key.

Next, the [D11: LOW CUT MODE]

setting panel is displayed.

a. Display Selection (D20: DISP SELECT)

Follow the instructions given to the below to change
the range of integral indication scales.

When USER SET is selected, the user set values of
integral indication and A11: ENGR. OUTPUT
parameter are indicated.

• Example: Set the integral indicator scale to

engineering units display.

The “%” disappears from the

integral indicator display.

ESC

SET
D20:DISP SELECT
USER SET

FEED

NO

OK

SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>

Use the or key

to select “USER SET.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0820.EPS