Pulse input function, Pulse input function -9 – Yokogawa Button Operated MV2000 User Manual

Page 24

Advertising
background image

3-9

SM MV1000-01E

Testing

1

2

3

4

5

6

7

3.4 Test Procedures

Pulse Input Function

● Overview

This test performed when the /PM1 option is specified. Enter calculation settings, input

a pulse signal, and perform the test.

● Test Instruments

Instrument

Specifications

Function generator

Accuracy: ±20ppm of setting for 100 Hz

● Setup

1.

Press the

MENU key, then choose Math channel > Calculation expression

(Expression).

2.

Enter the following expressions. Press the

ESC key to return to the setting menu.

• 101CH: Q06 (span: 0-100)
• 102CH: Q07 (span: 0-100)
• 103CH: Q08 (span: 0-100)

3.

Select

Group set, then set CH set to 101-103.

4.

Press the

ESC key twice to return to operation mode.

● Test Procedures

Input a pulse signal of 100 Hz and 0-5 V to input pulse terminals 6, 7, and 8, then

perform the test.

Reference value: 100 ±1